Specifications
General Specifications
Specification Value
Dimensions, HxWxD 90 x 40 x 87 mm (3.54 x1.58 x 3.43 in.)
height including mounting tabs is 110 mm (4.33 in.)
Approximate Shipping Weight
(with carton)
260 g (0.57 lbs.)
Storage Temperature -40…85 °C (-40…185 °F)
Operating Temperature 0…55 °C (+32…131 °F)
Operating Humidity 5…95% non-condensing
Operating Altitude 2000 m (6561 ft)
Vibration Operating: 10…500 Hz, 5 g, 0.030 in. max. peak-to-peak
Shock Operating: 30 g
Bus Current Draw (max.) 40 mA @ 5V DC
50 mA @ 24V DC
Heat Dissipation 1.5 Watts
Input Group to System Isolation
30V AC/30V DC rated working voltage
(1)
(N.E.C. Class 2 required)
(IEC Class 2 reinforced insulation)
type test: 500V AC or 707V DC for 1 minute
(1) Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth ground.
Module Power LED On: indicates power is applied.
Vendor I.D. Code 1
Product Type Code 10
Product Code 65
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
ISA/ANSI 12.12.01
(C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
ESD Immunity (EN61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (EN61000-4-3) 10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier
Fast Transient Burst (EN61000-4-4) 2 kV, 5 kHz
Surge Immunity (EN61000-4-5) 1 kV galvanic gun
Conducted Immunity (EN61000-4-6)
10V, 0.15…80 MHz
(2)
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.