Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous
locations only. The following WARNING statement applies to use in hazardous locations.
Use only the following communication cables in Class I, Division 2 hazardous locations.
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Division 2.
Do not replace components or disconnect equipment unless power has been switched
off.
Do not connect or disconnect components unless power has been switched off.
This product must be installed in an enclosure. All cables connected to the product
must remain in the enclosure or be protected by conduit or other means.
All wiring must comply with N.E.C. article 501-10(b) and/or in accordance with
Section 18-1J2 of the Canadian Electrical Code, and in accordance with the authority
having jurisdiction.
Environment Classification Communication Cables
Class I, Division 2 Hazardous Environment 1761-CBL-AC00 Series C or later
1761-CBL-AM00 Series C or later
1761-CBL-AP00 Series C or later
1761-CBL-PM02 Series C or later
1761-CBL-HM02 Series C or later
2707-NC9 Series C or later
1763-NC01 Series A or later
1747-CP3 Series