Installation Instructions Owner manual

MicroLogix 1400 Programmable Controllers 35
Publication 1766-IN001C-EN-P - October 2009
Certifications for 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA,
1766-L32BWAA, 1766-L32BXB, 1766-L32BXBA
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on AC power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±1 kV line-earth(CM) on communications ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation IEC 6100-4-11:
60% dip for 10 periods on AC supply ports
30% dips for 25 periods @ 0° and 180° on AC supply ports
100% dip for 250 periods @ 0° and 180° on AC supply ports
100% dip for 0.5 periods, arbitrary angle, on AC supply ports
Certification (when
product is marked)
(1)
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification
details.
Value
UL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations.
See UL File E10314.
c-UL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for
Canada. See UL File E10314.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Description 1766-L32AWA
1766-L32AWAA
1766-L32BWA
1766-L32BWAA
1766-L32BXB
1766-L32BXBA