User Manual Owner manual

Installing the KF3
Chapter 2
27
Figure 2.9
Connection
for Last Segment of a Multidrop Network
Third
node
Jumper to
terminate node
Fourth node on the end of the multidrop network
* The black wire of the white/black pair should be cut back (no connection).
DH485
Cable
Installing the DH485 Cable
The DH-485 cable consists of a number of daisy-chained segments. The
total length of the combined segments must not exceed 4,000 feet. Cut the
cable segments long enough to route from one node to the next, allowing
sufficient slack to prevent strain on the connectors. Provide strain relief
for the cable after it is plugged in to prevent the cable wires from breaking.
Figure 2.10
Cable
Connection on a DH485 Link
BELDEN
#9842
BELDEN
#9842
Connector
(Phoenix
MSTB2.5/6ST
AU)
KF3
Link
Coupler
1747AIC
Link
Coupler
1747AIC