User Manual PLC-3 FAMILY I/0 Instruction Manual
Binary Command Language
Appendix A
A-34
The processor responds to a delete command with one of the following
response codes:
Response Codes
Hex Description
00 Success
03 Unavailable - section does not exist
04 Address could not exist - invalid values
06 Access not allowed
08 Insufficient address - not specified to at least three levels
0F No privilege
The following example response block shows a successful
delete command:
STX
02
OSC
11
SIZ
01
RSP
00
ETX
03
CHK
17
LIST Command
Hex: 29
Parameters: none required
Description: The LIST command accesses the LIST function. This
command allows you to send ASCII characters to the processor. These
characters are interpreted in the same manner as if they were entered from
the processor front panel or the keyboard of a programming device
(see chapter 3).
The processor remains in the LIST processing mode until it receives either
a command block which does not contain a LIST command or a break
character. The following example command block uses the LIST
command (with no data in the command buffer):
STX
02
ISC
31
SIZ
01
CMD
29
ETX
03
CHK
60