User Manual PLC-3 FAMILY I/0 Instruction Manual

DH/DH+ Error Codes
Apendix B
B-7
Error Code MeaningAssociated
Commands
Error Type
209 local all Not of DH message type.
210 local all Use of a nonPLC3 type address in a local address operand.
211 local all In an assignment command, one of the local files does not exist, or the word
specified is beyond the end of the file.
212 local create During CREATE command execution, the scanner was not able to create any
symbols.
213 local all A local file exists, but the action specified refers to addresses beyond the end of
the file. Possible causes include:
In a word assignment statement, the offset is greater than the file size.
In a word range assignment statement, the sum of the base address and the
offset is greater than the total file size.
In a file assignment statement, the destination file is smaller than the source
file. If the source file is remote, a single packet is fetched from the remote
station's file.
214 local all Local source and destination files differ in size.
215 local all The value resulting from operations specified on the left side of an assignment
statement does not fit into the destination specified on the right side:
The source is in the H section and the destination is in the N section, but the
number is too large (i.e., outside the range -32768 to +32767).
A word is transferred from a binary section (I, O, or B section) to the N or C
section and the highorder bit is a 1.
The destination is in the decimal section, but the number is not a valid BCD bit
pattern.
217 local all More than eight levels specified in file address.
218 local all
File size changed between packets of a multipacket transaction.
Destination not created.
230 local all Reply packet too small.
231 reply PLC3 read and
write
Error in converting the block address (major section 63, context 15, or section
15).
232 reply PLC3 read and
write
Three or fewer addressing levels specified for a PLC3 word address.
233 reply PLC3 read and
write
Conversion of a file address to a block address resulted in more than nine
addressing levels.
234 reply PLC3 read and
write
Symbolic address not found.
235 reply PLC3 read and
write
Symbolic address is of length zero or is longer than eight bytes.