User Manual PLC-3 FAMILY I/0 Instruction Manual

Appendix
D
D-1
Specifications
Specification
Function
I/O communication
DH communication
DH+ communication
backup communication
peertopeer communication
frontpanel support
Location
1775S5 - single slot in a PLC3 chassis
1775SR5 - single slot in a PLC3/10 chassis
I/O Capacity per Scanner
2,048 I/O (any mix)
4,096 I/O (complementary)
Communication Rates (in kbps)
57.6 at 10,000 cable ft. (DH, DH+, I/O)
115.2 at 5,000 cable ft. (I/O only)
230.4 at 2,000 cable ft. (I/O only)
Cabling
Twinaxial Cable (cat. no. 1770CD) for I/O, DH or
DH+ communication channels
Industrial Terminal T50 Cable (cat. no. 1784CP5)
for DH+ communication to T50 industrial terminal
Nominal I/O Scan Times Per I/O
Adapter at 115.2Kbaud
4.5ms for 1 channel
5ms for 2 channels
5ms for 3 channels
6.5ms for 4 channels
8ms for 3 channels + DH
9ms for 3 channels + DH+
Backplane Current
6.0A maximum from +5V
20mA maximum from ±15V
Environmental Conditions
Operating Temperature: 0 to 60° C (32 to 140°F)
Storage Temperature: 40 to 85° C (40 to 185° F)
Relative Humidity: 5 to 95% (without condensation)