User Manual PLC-3 FAMILY I/0 Instruction Manual
Scanner Hardware and Installation
Chapter 1
1-16
The terminal arm provides connections for four I/O communication
channels (Figure 1.11). Functions of these channels include:
I/O communication
backup communication
peer-to-peer communication
If you select: Then the maximum I/O channel cable length can be:
57.6 kbps 10,000 feet
115.2 kbps 5,000 feet
230.4 kbps 2,000 feet
Important: If you set the protocol for channel four to a DH or DH+ link,
the scanner automatically disables the channel four terminals, and enables
the DH/DH+ connectors (see “Connecting to a DH or DH+ Network,”
page 1-13).
Figure 1.11
I/O
Channel T
erminal Arm Connections
Line 1
Shield
Line 2
Line 1
Shield
Line 2
I/O
Channel 4
I/O
Channel 2
Line 1
Shield
Line 2
Line 1
Shield
Line 2
Blue
Clear
1770XT
Terminator
I/O
Channel 3
I/O
Channel 1
15409
Twinaxial Cable
(cat. no. 1770CD)
Connects to a Remote I/O Device for I/O communication or a scanner
in another PLC3 or PLC3/10 chassis for peertopeer or backup communication.
If the scanner is at the end of the channel, set the terminator switch corresponding
to the channel number. If the channel is configured for I/O at 230.4 kbps, disable
the terminator for the channel and install an external 82 ohm terminator
(optional)
Connecting to the I/O
Channel Terminal Arm