User manual
4-8 Connect the Interface Card 
1784-6.5.22 - November 1999
Connect the Card via a DH-485 Network
Figure 4.1 shows an example of a network consisting of three SLC 500 
controllers and one programming station. This configuration requires the 
1784-KTX or -KTXD card and three link couplers:
• An SLC 500 CPU is connected to each of the link couplers (1747-AIC) with a 
1747-C11 cable.
• The 1784-KTX or -KTXD card is connected to the network at one of the link 
couplers, as shown in Figure 4.1.
• The communication cable consists of three segments of cable daisy-chained 
at each link coupler.
Figure 4.1 Communicate to multiple SLC 500s via the DH-485 network
To
1784-KT
x
 Card
Communication Cable
Belden #9842
Link 
Coupler
1747-AIC
Link 
Coupler
1747-AIC
Link 
Coupler
1747-AIC
1747-C11
1747-C11
1747-C11
SLC 500 Controller
SLC 500 Controlle
r
SLC 500 Controller
42139