Terminal Block (RTB)
The Removable Terminal Block (RTB) is provided on all 12-point and 
16-point discrete I/O modules and analog modules. They allow for 
faster and more convenient wiring of the I/O modules. The modules 
and the RTB are color-coded.
Replacement terminal blocks are available if they are lost or damaged. 
See the replacement part list in chapter 11.
Remove the RTB
Below are guidelines for removing the I/O Removable Terminal 
Block.
1. If the I/O module is already installed in the chassis, remove 
power to the SLC chassis.
2. Unscrew the upper right and lower left terminal block release 
screws.
3. Grasp the RTB with your thumb and forefinger and pull straight 
out.
4. Label the RTB with appropriate slot, chassis, and module 
identification.
Color Type of I/O Removable Terminal Block
Red ac inputs/outputs
Blue dc inputs/outputs
Orange relay outputs
Green specialty modules
ATTENTION
Never install or remove I/O modules or terminal blocks while 
the SLC chassis is powered.
Terminal Block 
Release Screw
Terminal Block 
Release Screw
Dot indicates Terminal Number 0 