Installation Instrucitons Owner manual
7-2 Interpret Status Indicators
Publication 1784-IN042A-EN-P - April 2005
• flashing - the indicator alternates between the two defined states (applies to each
indicator viewed independent of the other). If both indicators flash, they must flash
together, in phase.
Table 7.1 ControlNet status interpretation
A and B
Cause: Action:
off • no
power • none or apply power to the PC
• 17
84-PKTCS card
not configured
• Configure the card. See page 5-2.
• 17
84-PKTCS
driver not
installed
• I
nstall the driver. Refer to Chapter 3.
• f
aulted card • check operating system event log for details
of fault (if the PC’s operating system supports
an event log)
• cycle
power to the PC
• ve
rify that you have firmly inserted the
1784-PKTCS card into a PCI local bus
expansion slot and that the expansion slot
screw is tightened
• i
f fault persists, contact your Rockwell
Automation representative or distributor
steady red • f
aulted card • check operating system event log for details
of fault (if the PC’s operating system supports
an event log)
• cycle
power to the PC
• ve
rify that you have firmly inserted the
1784-PKTCS card into a PCI local bus
expansion slot and that the expansion slot
screw is tightened
• i
f fault persists, contact your Rockwell
Automation representative or distributor
alternating red/green • se
lf-test • none
alternating red/off • i
ncorrect node
configuration
• d
uplicate
ControlNet node
address
• c
heck 1784-PKTCS node address and other
ControlNet configuration parameters
off • c
hannel disabled • use RSNetWorx to configure the ControlNet
network for redundant media, if required