Installation Instructions

ControlNet Fiber-optic Ring Repeater Modules 31
Rockwell Automation Publication 1786-IN003D-EN-P - April 2011
Flashing red/off Module is powered, but not
ready for operation. This
state should also occur
during module reset and last
for approximately
5 seconds.
Do nothing. The fiber
repeater module is
operating properly.
Intermittent red As more data errors are
detected the frequency of
the flashing red increases
until a solid red displays.
Check for proper operation.
Red Excessive receive signal
distortion.
Review these items:
Be certain that you are
using the correct fiber
type for your module.
Check fiber length and
attenuation to make sure
that it is within
specification.
Replace the downstream
1786-RPFRL module on
the channel that is
having the intermittently
flashing red status
indicator.
Be certain that your total
network length is not out
of specification.
Be certain that SMAX is
correctly defined in the
RSNetWorx for
ControlNet software.
Table 3 - Fiber Repeater Module Status Indicators
If the fiber repeater
module indicator is
This means You should