User Manual Owner's manual
Rockwell Automation Publication 1789-UM002J-EN-P - December 2012 19
Chapter 1
The RSLinx software module defaults in Slot 0 if not set up for another slot position.
6. From the Slot Number pull-down menu, choose a slot number.
7. Click OK and then click Close.
Troubleshoot the SoftLogix 5800 Controller
This table describes the status of the controller.
IMPORTANT
Even if you remotely program the controller over a ControlNet or Ethernet link, you must
add the virtual-backplane driver via RSLinx software. If you do not, the SoftLogix
application will not be restored when you restart the computer.
Table 1 - Troubleshooting the Controller
Indicator Status Description
RUN Off The controller is in Program or Test mode.
Green The controller is in Run mode.
I/O Off Either of these is true:
• There are no devices in the I/O configuration.
• The controller does not contain a project (controller memory is empty).
Green The controller is communicating with all the devices in its I/O configuration.
Green flashing One or more devices in the I/O configuration of the controller are not responding.
Red flashing A virtual chassis error was detected. Contact your Rockwell Automation
representative or local distributor.
FRC Off No tags contain force values.
Forces are inactive (disabled).
Flashing At least one tag contains a force value.
Force values are inactive (disabled).
Green Forces are active (enabled).
Force values may or may not exist.
RS232
(1)
Off No COM port was selected.
Green The selected COM port was successfully assigned to channel 0 on the controller.
Red There is a COM port conflict or you selected an invalid COM port number.
BAT
(1)
Off Normal operation.
Amber flashing The controller is in Power-up mode.
Red Persistent storage for the controller has failed.