Installation Instructions ArmorBlock MaXum 8 Input / 8 Output Module Series B (Cat. No. 1792D-8BVT8D) 41516 This ArmorBlock MaXum™ I/O module (Cat. No. 1792D-8BVT8D) is a stand-alone 24V dc I/O product which communicates via a DeviceNet™ network. The sealed housing of this module requires no enclosure. This model has 8 inputs and 8 outputs accessed through Y splitter cables. Inputs are 24V dc automatically configured for PNP (sourcing) or NPN (sinking) devices.
ArmorBlock MaXum 8 Input / 8 Output Module Series B Package Contents Your package contains: • 1 ArmorBlock MaXum Module • Installation Instructions (Note: Cable bases are ordered and shipped separately.) European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
ArmorBlock MaXum 8 Input / 8 Output Module Series B 3 Install Your ArmorBlock MaXum I/O Module To install module: • • • • Set the node address Mount the module to the cable base Connect the cord sets Communicate with the module Set the Node Address Valid node addresses are 00 to 63. Set the node address using the rotary switches, RSNetWorx for DeviceNet™, DeviceNetManager™, or other software configuration tool. Setting the switches between 64 to 99 lets the software have address control.
ArmorBlock MaXum 8 Input / 8 Output Module Series B The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings. Install the Module This module mounts to the following cable bases: • • • • 1792D-CBFM for KwikLink™ flat media installation 1792D-CB12 for 12mm drop cable installation 1792D-CB18P for round media DeviceNet and output power or other optional cable base assembly.
ArmorBlock MaXum 8 Input / 8 Output Module Series B 5 Note: Dimensions change according to the cable base and module combination used. 2.7 (68.6) 6.85 (174mm) Assembled dimensions in (mm) 1.9 (48.26) Align the screws to properly assemble the module to the base. Cable Base 1792D-CBFM is used for this example. 41522 Connect the Input / Output Cord Sets to the MaXum Module This module uses 5 pin micro (12mm) style PCB mounted connectors. Eight micro caps cover the connectors on your module.
ArmorBlock MaXum 8 Input / 8 Output Module Series B Use the micro caps to cover and seal unused ports. Pinout diagrams for the connectors are shown next. Input Micro-Connector (View into Socket) Pin 1 Sensor Source voltage Pin 2 Input B Pin 3 Return Logic Ground1 Pin 4 Input A Pin 5 Not Used Output Micro-Connector (View into Socket) Pin 1 Not Used Pin 2 Output B Pin 3 Auxiliary Power Ground Pin 4 Output A Pin 5 Not Used 1Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.
ArmorBlock MaXum 8 Input / 8 Output Module Series B 7 • Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements. • For maximum noise immunity, input and output cable return wires must be properly terminated. When inputs and outputs are connected in loopback, return wires should be connected together. • I/O cable length should be less than 30 meters. ATTENTION ! I/O connectors for this module are shown below.
ArmorBlock MaXum 8 Input / 8 Output Module Series B Communicate With Your ArmorBlock MaXum I/O Module This ArmorBlock module’s I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. The module consumes and produces I/O data as follows: Type of I/O Connections Consumes Produces Cyclic 1 Byte 4 Bytes Polled 1 Byte 4 Bytes Change-of-State 1 Byte 4 Bytes Cyclic - allows configuration of the block as an I/O client.
ArmorBlock MaXum 8 Input / 8 Output Module Series B 9 Byte Bit Description Produces 0 00-07 Input Status bits: When the bit is set (1), the input is on. Bit 00 = to input 0, bit 01 = to input 1, bit 02 = to input 2, bit 03 = to input 3, bit 04 = to input 4, bit 05 = to input 5, bit 06 = to input 6, bit 07 = to input 7.
ArmorBlock MaXum 8 Input / 8 Output Module Series B Troubleshoot with the Indicators This module has the following indicators: • • • • Network and Module status indicator Logic status indicator Auxiliary Power indicator Individual I/O status indicators for inputs 0 through 7 and outputs 0 through 7.
ArmorBlock MaXum 8 Input / 8 Output Module Series B 11 Net/Mod Status Indicator (continued) Solid Red Unrecoverable fault Communication failure - duplicate node address present or incorrect baud rate Green to Red to Off At powerup only - LED test The following table describes logic status indicators.
ArmorBlock MaXum 8 Input / 8 Output Module Series B Specifications 8 Input / 8 Output Module - Cat. No. 1792D-8BVT8D Input Specifications Max. Inputs per block 8 - 3 wire or dry contact PNP or NPN devices or 4 4 wire PNP or NPN devices Sensor Source Current (per connector) 100mA total - Off-Wire Sense Current 0.5mA - On-state Voltage 25V dc 10V dc On-state Current 10mA 2mA Off-state Voltage 5V dc - Off-state Current - 1.5mA Output Specifications Max. Outputs per block Min.
ArmorBlock MaXum 8 Input / 8 Output Module Series B 8 Input / 8 Output Module - Cat. No. 1792D-8BVT8D General Specifications Auxiliary Power Voltage Current Dimensions (assembled to base) inches - (Millimeters) Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Non-operating Vibration 30V dc max 4A max 10V dc min 4A max 1.9H x 2.7W x 6.85D (48.26)H x (68.
ArmorBlock MaXum 8 Input / 8 Output Module Series B Hazardous Location Approval The following information applies only to products marked with Hazardous Location Approval, when operating in hazardous locations: Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code.
ArmorBlock MaXum 8 Input / 8 Output Module Series B WARNING ! 15 When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
AVERTISSEMENT ! AVERTISSEMENT ! Utiliser des fils d’alimentation qui conviennent à une température de 30°C au-dessus de la température ambiante. Pour une utilisation en environnement de classe i, division 2 dangereux, cet equipement doit etre monte dans un boitier avec un cablage approprie conforme aux normes electriques en vigueur. This product has been tested at an Open DeviceNet Vendor Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test.