Publication 1794-UM066A-EN-P - February 2012
Rack Optimized Discrete I/O 35
1. Click on the Communications menu and select Who Active.
The Who Active window opens .
2. Select your Ethernet driver (for example, AB_ETH-1) and expand the tree
through the backplane of the local ControlLogix chassis.
3. Highlight the Logix5572 controller and click Download.
A Download dialog appears:
4. Click Download.
The program downloads to the controller.
5. Minimize the RSLogix 5000 software.
Test the Example
Application
Test the example application by using a momentary switch to simulate a parts
sensor.