Owner manual
Table Of Contents
- 1794-UM066A-EN-P FLEX I/O Dual Port EtherNet/IP Adapter Modules User Manual
- Important User Information
- Preface
- Table of Contents
- 1 - Overview of FLEX I/O and Your Redundant EtherNet/IP Adapter Module
- Overview
- The FLEX I/O System
- Adapter Features
- Types of Adapters
- Hardware and Software Compatibility
- What the Adapter Does
- Use of the Control and Information Protocol (CIP)
- Understanding the Producer/Consumer Model
- Specifying the Requested Packet Interval (RPI)
- Support of Rack Optimized and Direct Connections
- Chapter Summary
- 2 - Install Your FLEX I/O Adapter
- 3 - Configure the Adapter for Your EtherNet/IP Network
- 4 - Rack Optimized Discrete I/O
- 5 - Analog I/O with Direct Connection
- A - Interpret Status Indicators
- B - Specifications
- C - Configure the RSLinx Ethernet Communication Driver
- D - Adapter Web Dialogs
- Index
- Back Cover
Publication 1794-UM066A-EN-P - February 2012
48 Analog I/O with Direct Connection
2. Select your Ethernet driver (for example, AB_ETH-1) and expand the tree
through the backplane of the local ControlLogix chassis.
3. Highlight the controller. and then click Download to download the
program to the Logix5572 controller.
A Download dialog appears:
4. Click Download.
The program downloads to the controller.
5. Minimize the RSLogix 5000 software window.
Test the Example
Application
Use the following procedure to test the operation of the FLEX analog input and
output modules:
1. Connect analog output channel 0 on the 1794-OF4I/A module to analog
input channel 0 on the 1794-IF4I/A input module.
2. Restore the RSLogix 5000 software window and place the controller in
Run mode.
3. Double-click the Controller Tags folder, and then select the Monitor tab.
VR
23
VR
23
1794-IF4I 1794-OF4I