Owner manual
Table Of Contents
- 1794-UM066A-EN-P FLEX I/O Dual Port EtherNet/IP Adapter Modules User Manual
- Important User Information
- Preface
- Table of Contents
- 1 - Overview of FLEX I/O and Your Redundant EtherNet/IP Adapter Module
- Overview
- The FLEX I/O System
- Adapter Features
- Types of Adapters
- Hardware and Software Compatibility
- What the Adapter Does
- Use of the Control and Information Protocol (CIP)
- Understanding the Producer/Consumer Model
- Specifying the Requested Packet Interval (RPI)
- Support of Rack Optimized and Direct Connections
- Chapter Summary
- 2 - Install Your FLEX I/O Adapter
- 3 - Configure the Adapter for Your EtherNet/IP Network
- 4 - Rack Optimized Discrete I/O
- 5 - Analog I/O with Direct Connection
- A - Interpret Status Indicators
- B - Specifications
- C - Configure the RSLinx Ethernet Communication Driver
- D - Adapter Web Dialogs
- Index
- Back Cover
Publication 1794-UM066A-EN-P - February 2012
68 Adapter Web Dialogs
• Received / Transmitted packets
• Connection ID
•Source
•Destination
• Multicast Address
•RPI
• Lost Packets
•Size
Work with the
Configuration Pages
To work with the Configuration pages, follow these procedures.
1. From the Home page, click Configuration or Expand to see the
Configuration options, if needed.
2. From the Configuration page, click one of the following:
•Identity
•Network
•Services
IMPORTANT
The values on these pages are in non-volatile memory. Changes to these
parameters do not take effect until you reset or cycle power through the
FLEX I/O adapter.
IMPORTANT
If you set the value of the adapter switch to 888 and then power cycle the
module, the following occurs:
• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically. The Auto Negotiate
function is set to True.
• The web server is enabled. The Disabled Web Server function is
disabled.
• The Ethernet port are disabled. Both ports are re-enabled once the
switches are returned to their previous value and power is cycled.
• The password for this page resets to the factory default which is
"<blank>".
Note the value of the switches before you enter the 888 value because
you must return the adapter to those values once this process is
complete.