Installation Instructions User guide

26 FLEX I/O 8 Input HART Analog Module
Publication
1794-IN108D-EN-P - January 2014
The extended configuration data table is accessed (read/write) by using a
MSG or CIO instruction. Refer to Field Descriptions on page 27 for more
information.
Error Level 0.1 mA Steps (Series A Mode)
Word Bits Description
Word 0 13 12 11 10 09 Error level channels 0...3
W
ord 1 13 12 11 10 09 Error level channels 4...7
00000Disabled
0.1 mA * binary valve = remote fault alarm
Examples
Data Format
2...22 mA
-12.5...112.5%
Binary
value = 7, 0.1 mA * 7 = 0.7 mA
Remote fault alarm at -4.38% or +104.38%
Binary value = 15, 0.1 mA * 15 = 1.5 mA
Remote fault alarm at -9.38% or + 109.38%
Extended Configuration Data Table (Series A Mode)