User Manual User guide

50 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
1. Write the appropriate ladder logic to execute a MSG instruction for the
MicroLogix controller (an EEM instruction for the SLC-5/05) to control
the E1 Plus EtherNet/IP Side Mount Module.
2. Configure General tab in the MSG instruction with the following
parameters:
Channel: 1 (Integral) - the Ethernet port on the processor
Communication Command: CIP Generic
Data Table Address: the location to write the information from
Size in Bytes: 1 – assembly 101 consists of 1 byte of information
MultiHop: Yes
Service: Write Assembly – to write an output assembly
Class: 4 – the Assembly Object
Instance: 101 – the Basic Contact output assembly
Attribute: 3 – get/set data instance attribute