Chapter 6
Advanced Setup Group
Trip Status Parameter No. 3
This parameter provides trip identification.
1 = Trip
0 = No Trip
Bit 0: Overload — Tag Name: Trip_Status: Overload
Bit 1: Phase Loss — Tag Name: Trip_Status: Phase_Loss
Bit 2: Jam — Tag Name: Trip_Status: Jam
Access Rule Get
Data Type WORD
Units
Min. Value 0x0000
Max. Value 0x0007
Default Value 0x0000
Warning Status Parameter
No.
4
This parameter provides warning identification
1 = Warning
0 = No Warning
Bit 0: Overload — Tag Name: Warning_Status: Overload
Bit 2: Jam — Tag Name: Warning_Status: Jam
Bit 3: Underload — Tag Name: Warning_Status: Underload
Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault
Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle
Bit 7: Non Vol Mem Fault — Tag Name: NV_Mem_Fault
Access Rule Get
Data Type WORD
Units
Min. Value 0x0000
Max. Value 0x00FF
Default Value 0x0000
Device Status Parameter
No.
10
This parameter provides status information related to the E1 Plus
Overload Relay and the SMM.
1 = On or Present
0 = Off or Not Present
Bit 0: Trip — Tag Name: Device_Status: Trip
Bit 1: Warning — Tag Name: Device_Status: Warning
Bit 2: Output A — Tag Name: Device_Status: Out_A
Bit 3: Input #1 — Tag Name: Device_Status: In_1
Bit 4: Input #2 — Tag Name: Device_Status: In_2
Bit 5: Motor Current — Tag Name: Device_Status: Motor_Current
Access Rule Get
Data Type WORD
Units
Min. Value 0x0000
Max. Value 0x003F
Default
Value
0x0000
Trip Enable Parameter No. 12
This parameter allows the installer to enable or
disable the Jam Trip function
1 = Enabled
0 = Disabled
Bit 2: Jam— Tag Name: Trip_Enable: Jam
Access Rule Get/Set
Data Type WORD
Units
Min. Value 0x0000
Max. Value 0x0007
Default Value 0x0000