66 Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 6
Warning Enable Parameter
No.
13
This parameter allows the installer to enable or disable the warning
functions separately. All warning functions are disabled from the
factory.
1 = Enabled
0 = Disabled
Bit 0: Overload — Tag Name: Warning_Status: Overload
Bit 2: Jam — Tag Name: Warning_Status: Jam
Bit 3: Underload — Tag Name: Warning_Status: Underload
Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault
Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle
Access Rule Get/Set
Data Type WORD
Units
Min. Value 0x0000
Max. Value 0x007F
Default Value 0x0000
Single/Three Ph Parameter No. 15
This parameter configures the EtherNet/IP
Module for single- or three-phase application.
This parameter should be set to “Single Phase"
when Bulletin 193S or 592S devices are
employed.
0 = Single Phase
1 = Three Phase
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 1
Tag Name Single_Three_Ph
OL Reset Mode Parameter No. 16
This parameter defines whether a trip can be
automatically or manually reset. This setting
overrides the E1 Plus DIP switch adjustment while
the SMM is powered. Note, however, that the E1
Plus manual reset button, accessible at the front,
is always active.
0 = Manual
1 = Automatic
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OL_Reset_Mode
OL Warning Level Parameter No. 17
This parameter sets the overload warning level. Access Rule Get/Set
Data Type USINT
Units % TCU
Min. Value 0
Max. Value 100
Default Value 90
Tag Name OL_Warning_Level