Rockwell Automation Publication 193-UM012B-EN-P - June 2011 67
Chapter 6
Jam Inhibit Time Parameter No. 18
This parameter defines the amount of time for
which jam detection is inhibited during a motor
starting sequence.
Access Rule Get/Set
Data Type USINT
Units Seconds
Min. Value 0
Max. Value 250
Default Value 10
Tag Name Jam_Inhibit_Time
Jam Trip Delay Parameter No. 19
This parameter allows the installer to program a
time duration for which a jam condition must exist
at the programmed level prior to the device
tripping.
Access Rule Get/Set
Data Type USINT
Units Seconds
Min. Value 5
Max. Value 250
Default Value 50
Tag Name Jam_Trip_Delay
Jam Trip Level Parameter No. 20
This parameter sets the jam trip level. Access Rule Get/Set
Data Type UINT
Units % FLA
Min. Value 150
Max. Value 600
Default Value 250
Tag Name Jam_Trip_Level
Jam Warn Level Parameter No. 21
This parameter sets the jam warning level. Access Rule Get/Set
Data Type UINT
Units % FLA
Min. Value 100
Max. Value 600
Default Value 150
Tag Name Jam_Warn_Level