Reset/Lock Group
UL Inhibit Time Parameter No. 22
This parameter defines the amount of time for
which underload detection is inhibited during a
motor starting sequence.
Access Rule Get/Set
Data Type USINT
Units Seconds
Min. Value 0
Max. Value 250
Default Value 10
Tag Name UL_Inhibit_Time
UL Warn Level Parameter No. 23
This parameter sets the underload warning level. Access Rule Get/Set
Data Type USINT
Units % FLA
Min. Value 30
Max. Value 100
Default Value 70
Tag Name UL_Warn_Level
Trip Reset Parameter No. 14
This parameter provides the user with the
capability of resetting a trip over the EtherNet/IP
network. After a trip is reset, the parameter
automatically returns to a “Ready” state.
0 = Ready
1 = Reset Trip
Note: A transition from 0 to 1 is necessary to
trigger a trip reset when mapped on the cyclic
data.
Access Rule Get/Set
Data Type BOOL
Units —
Min. Value 0
Max. Value 1
Default Value 0
Tag Name Trip_Reset
Program Lock Parameter No. 24
This parameter prohibits the device parameters
from being altered when set to “Locked”. It must
be set to “Unlocked” to allow parameter
modification.
It doesn’t affect parameters when they’re
accessed through the assembly object.
0 = Unlocked
1 = Locked
Access Rule Get/Set
Data Type BOOL
Units —
Min. Value 0
Max. Value 1
Default Value 0
Tag Name Program_Lock