Rockwell Automation Publication 193-UM012B-EN-P - June 2011 69
Chapter 6
I/O Setup Group
Set To Defaults Parameter No. 25
This parameter allows the user to reset the
parameter settings to the factory default values.
After parameter values have been reset to the
factory default settings, the parameter
automatically returns to a “Ready” state.
0 = Ready
1 = Reset Defaults
Note: A transition from 0 to 1 is necessary to
trigger a set to default when mapped on the cyclic
data.
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name Set_To_Default
OutA Pr FltState Parameter No. 34
This parameter, in conjunction with the Pr
FltValue, defines how Output A will respond when
a trip occurs. When set to “1”, Output A will
continue to operate as commanded via the
network. When set to “0”, Output A will open or
close as determined by the setting of the Pr
FltValue.
0 = Go to FltValue
1 = Ignore Fault
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OutA_Pr_FLTState
OutA Pr FltValue Parameter No. 35
This parameter determines the state that Output A
assumes when a trip occurs and the Pr FltState is
set to “0”.
0 = Open
1 = Closed
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OutA_Pr_FLTValue
OutA En FltState Parameter No. 36
This parameter, in conjunction with the FltValue,
defines how Output A will respond when a
EtherNet/IP network fault occurs. When set to
“1”, Output A will hold the state prior to trip
occurrence. When set to “0”, Output A will open
or close as determined by the setting of the
FltValue.
0 = Go to FltValue
1 = Hold Last State
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OutA_En_FLTState