OutA En FltValue Parameter No. 37
This parameter determines the state that Output A
assumes when a EtherNet/IP network fault occurs
and the FltState is set to “0”.
0 = Open
1 = Closed
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OutA_En_FLTValue
OutA En IdlState Parameter No. 38
This parameter, in conjunction with the IdlState,
defines how Output A will respond when the
EtherNet/IP network is idle (clear mode). When
set to “1”, Output A will hold the state prior to trip
occurrence. When set to “0”, Output A will open
or close. The En Flt parameters supersede the En
Idl parameters.
0 = Go to IdlValue
1 = Hold Last State
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OutA_En_IdlState
OutA En IdlValue Parameter No. 39
This parameter determines the state that Output A
assumes when the network is idle and instructed
by the IdlState parameter.
0 = Open
1 = Closed
Access Rule Get/Set
Data Type BOOL
Units
Min. Value 0
Max. Value 1
Default Value 0
Tag Name OutA_En_IdlValue
IN1 Assignment Parameter No. 40
This parameter allows the user to assign a
specific function to the discrete IN1 input.
0 = Normal
1 = Trip Reset
2 = OL Contact
Access Rule Get/Set
Data Type USINT
Units
Min. Value 0
Max. Value 2
Default Value 0
Tag Name IN1_Assignment