Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012 67
Troubleshooting Chapter 7
MOD Status Indicator
This red/green bicolor LED indicates the status of the option module as shown
in the table below.
NET A Status Indicator
This red/green bicolor LED indicates the status of the Profibus connection to
the 20-750-PBUS option module as shown in the table below.
Status Cause Corrective Action
Off The option module is not powered or
connected properly to the drive.
Securely connect and ground the option module to
the drive by fully inserting it into the drive port and
tightening its two captive screws to the
recommended torque.
Apply power to the drive and network.
Flashing Red The option module has failed the firmware
test.
Cycle power to the drive. Parameter settings may
have been changed.
Clear faults in the option module.
If cycling power does not correct the problem, the
option module parameter settings may have been
corrupted. Reset defaults and reconfigure the option
module.
If resetting defaults does not correct the problem,
update the option module with the latest firmware
revision.
Steady Red The option module has failed the
hardware test.
Cycle power to the drive.
Replace the option module.
Flashing Green The option module is operational but is
not transferring I/O data.
Place the master in RUN mode.
Configure the option module for the program in the
controller.
Program the controller to recognize and transmit I/O
to the option module.
Normal behavior if no I/O is being transferred.
Steady Green The option module is operational and is
transferring I/O data.
No action required.
Status Cause Corrective Actions
Off The option module cannot establish
network communication or has
experienced a Communication Timeout.
Securely connect the option module to the drive and
connect it to the network using a Profibus cable.
Correctly connect the Profibus cable to the Profibus
connector.
Apply power to the drive.
Flashing Red The option module has detected a
Network Configuration Error.
Re-configure the Profibus module.
Steady Red The option module has experienced an
internal network controller error (Profibus
ASIC Self-Test failure).
Cycle power to the drive.
Re-configure the Profibus master.
Steady Green The option module is properly connected
and communicating over the Profibus
network.
No action required.