B-4 Adapter Parameters
20-COMM-L LonWorks Adapter User Manual
Publication 20COMM-UM008B-EN-P
21 [Send Service Pin]
Broadcasts a LON Service Pin Message from the
Neuron Chip. This provides the Neuron ID.
An alternate method for providing the Neuron ID is to
enter the ID number manually. The Neuron ID can be
viewed using Diagnostic Item # 30 (see page 5-4
).
Default: 0 = Ready
Values: 0 = Ready
1 = Send
Type: Read/Write
Reset Required: No
22 [Clear Counters]
Clears the network diagnostic counters (Diagnostic
Items # 26 and 27; see page 5-4
).
Default: 0 = Ready
Values: 0 = Ready
1 = Clear
Type: Read/Write
Reset Required: No
23 [DrvSpeedParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nvoDrvSpeed (see page 4-10
).
Setting this parameter value to ‘0’ disables the adapter
from retrieving the corresponding parameter value
from the drive.
Default: 1
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
24 [DrvCurntParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nvoDrvCurnt (see page 4-9
).
Setting this parameter value to ‘0’ disables the adapter
from retrieving the corresponding parameter value
from the drive.
Default: 3
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
25 [DrvPwrParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nvoDrvPwr (see page 4-10
).
Setting this parameter value to ‘0’ disables the adapter
from retrieving the corresponding parameter value
from the drive.
Default: 7
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
26 [DrvVoltParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nvoDrvVolt (see page 4-10
).
Setting this parameter value to ‘0’ disables the adapter
from retrieving the corresponding parameter value
from the drive.
Default: 6
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
27 [DrvRunHoursParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nvoDrvRunHours (see page 4-11
).
Setting this parameter value to ‘0’ disables the adapter
from retrieving the corresponding parameter value
from the drive.
Default: 10
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
28 [DrvFrqActParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nvoDrvFreqAct (see page 4-11
).
Setting this parameter value to ‘0’ disables the adapter
from retrieving the corresponding parameter value
from the drive.
Default: 1
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
29 [NmlFreqParam]
Sets the PowerFlex 7-Class drive parameter number to
be used with nciNmlFreq (see page 4-11
).
Default: 43
Values: PowerFlex 7-Class
drive parameter
numbers
Type: Read/Write
Reset Required: Yes
Parameter
No. Name and Description Details