User guide

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013 39
Configure Your Expansion I/O Module Chapter 5
2085-IRT4
For the RTD and Thermocouple expansion I/O, 2085-IRT4, you can configure
sensor type, data format, temperature units, and other properties, on each of the
four individual channels.
Configuration Parameters for 2085-IRT4
Configuration Property What to do Description
Enable channel Click the box to enable. This parameter enables the particular
channel for operation.
Sensor Type Select from the following
sensors:
100Ω Platinum 385
200Ω Platinum 385
100Ω Platinum 3916
200Ω Platinum 3916
100Ω Nickel 618
200Ω Nickel 618
120Ω Nickel 672
100Ω Copper 427
0…500 Ohm
0…100 mV
Thermocouple B
Thermocouple C
Thermocouple E
Thermocouple J
Thermocouple K
Thermocouple TXK/XK (L)
Thermocouple N
Thermocouple R
Thermocouple S
Thermocouple T
Defines the RTD or Thermocouple sensor
type for the channel.