User guide

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013 41
Configure Your Expansion I/O Module Chapter 5
Filter Update Time Set as the following (in
msec):
4
8
16
32
40
48
60
101
120
160
200
240
320
480
See Filter frequency on page 14
.
NOTE: Filter update time 4 ms is not
available for Thermocouple sensor types
B, R, S, E, J, C, K, L, N, or T or 0…10 mV.
Filter update time 8 ms is not available
for Thermocouple sensor types B, R, S.
Filter Frequency (-3dB) Set as the following (in Hz):
114
60
30
14
12
9.4
8.0
4.7
4.0
3.0
2.4
2.0
1.5
1.0
50/60 Hz Noise Rejection Set as:
Both (default)
50 Only
60 Only
Neither
See Noise Rejection on page 10
.
Configuration Parameters for 2085-IRT4
Configuration Property What to do Description