User guide
Rockwell Automation Publication 2080-UM003A-EN-E - March 2013 49
Specifications Appendix A
Off-state current, max 2.5 mA
On-state current, min 5.0 mA @ 74V AC 4.0 mA @ 159V AC
On-state current, max 12.5 mA @ 120V AC 7.0 mA @ 240V AC
Input impedance, max 22.2 kΩ
Inrush current, max 450 mA
Input filter time
Off to On
On to Off
<
20 ms
IEC type compliance Type 3
Output Specifications – 2085-OA8
Attribute 2085-OA8
Number of inputs 8
Voltage category 120V/230V AC
Operating voltage range 120…240V AC, 50/60 Hz
Output voltage, min 85V AC
Output voltage, max 240V AC
Off-state leakage current, max 2.5 mA
On-state current, min 10 mA per output
On-state current, max 0.5 A per output
On-state current, per module, max 4 A
Off-state voltage drop, max 1.5V AC @ 0.5 A
2.5V AC @10 mA
Fusing Not protected. A suitable rating fuse is recommended to
protect outputs.
Output signal delay
Off to On
On to Off
9.3 ms for 60 Hz, 11 ms for 50 Hz
9.3 ms for 60 Hz, 11 ms for 50 Hz
Surge current, max 5 A
2085-OW8 and 2085-OW16 Relay Output Module
Attribute 2085-OW8 2085-OW16
Number of outputs 8, relay 16, relay
Dimensions, HxWxD 28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)
44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)
Shipping weight,
approx.
140 g (4.93 oz) 220 g (7.76 oz)
Wire size
Insulation strip length 10 mm (0.39 in.)
Input Specifications – 2005-IA8 and 2085-IM8
Attribute 2085-IA8 2085-IM8
Min Max
Solid 0.34 mm
2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)