This workbook is Publication # PFLEX-IN002A-EN-P Last Reveision 1/21/02 These records can be printed to provide a written record of parameter changes made to a PowerFlex 70 or PowerFlex 700 drive. Some manpulation of the spreadsheets may be necessary based on you selection of a printer.
S.M.A.R.T. Start Parameter Setup Identity Customer Name Plant Machine # Process Number Other Data ____________________ ____________________ ____________________ ____________________ ____________________ Date Programmed ____________________ SW Version Drive Cat # Drive Ser # ____________________ ____________________ ____________________ Par Parameter Name Factory Default 40 Motor Type 41 Motor NP Volts Induction 42 Motor NP FLA Based on Drive Rating 43 Motor NP Hertz Based on Drive Cat.
Par Parameter Name Factory Default Programmed Value Par Parameter Name Factory Default 288 Stop Owner Read Only 1 Output Freq Read Only 289 Start Owner Read Only 2 Commanded Freq Read Only 290 Jog Owner Read Only 3 Output Current Read Only 291 Direction Owner Read Only 4 Torque Current Read Only 292 Reference Owner Read Only 5 Flux Current Read Only 293 Accel Owner Read Only 6 Output Voltage Read Only 294 Decel Owner Read Only 7 Output Power Read Only 295 Fa
Par Parameter Name Factory Default Programmed Value Par Parameter Name Factory Default 101 Preset Speed 1 5.0 Hz 195 MOP Rate 102 Preset Speed 2 10.0 Hz 196 Param Access Lvl 1.0 Hz/s Basic 103 Preset Speed 3 20.0 Hz 197 Reset To Defalts Ready 104 Preset Speed 4 30.0 Hz 198 Load Frm Usr Set Ready 105 Preset Speed 5 40.0 Hz 199 Save To User Set Ready 106 Preset Speed 6 50.0 Hz 200 Reset Meters 107 Preset Speed 7 60.
PowerFlex 70 Parameter Record
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par 1 Parameter Name Output Freq Minimum Value - [Maximum Freq] 2 3 4 5 6 7 8 9 10 11 12 13 Commanded Freq Output Current Torque Current Flux Current Output Voltage Output Power Output Powr Fctr Elapsed MWh Elapsed Run Time MOP Frequency DC Bus Voltage DC Bus Memory - [Maximum Speed] 0.0 Amps Drive Rating x -2 Drive Rating x -2 0.0 VAC 0.0 kW 0.00 0.0 MWh 0.0 Hrs - [Maximum Frequency] Based on Drive Rating Based on Drive Rating 0.
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name Minimum Value 90 Speed Ref A Sel 91 92 93 Speed Ref A Hi Speed Ref A Lo Speed Ref B Sel - [Maximum Speed] - [Maximum Speed] + + 94 95 Speed Ref B Hi Speed Ref B Lo - [Maximum Speed] - [Maximum Speed] + + Maximum Value Factory Default Analog In 1 Analog In 2 Reserved Reserved Reserved Reserved Reserved Reserved Reserved MOP Level Reserved Preset Spd1 Preset Spd2 Preset Spd3 Preset Spd4 Preset Spd5 Preset
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 96 TB Man Ref Sel 97 98 100 101 102 103 104 105 106 107 117 TB Man Ref Hi TB Man Ref Lo Jog Speed Preset Speed 1 Preset Speed 2 Preset Speed 3 Preset Speed 4 Preset Speed 5 Preset Speed 6 Preset Speed 7 Trim In Select 118 Trim Out Select 119 120 121 122 123 124 Trim Hi Trim Lo Slip RPM @ FLA Slip Comp Gain Slip RPM Meter PI Configuration 125 PI Control Minimum Value - [Maximum [Maximum [Maximum [Maximum [
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 126 PI Reference Sel 127 128 PI Setpoint PI Feedback Sel 129 130 131 132 133 PI PI PI PI PI Integral Time Prop Gain Lower Limit Upper Limit Preload Minimum Value -100.00% of Maximum Process Value 0.00 Secs 0.00 -400.0 Hz -400.0 Hz -400.
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name Minimum Value 134 PI Status 135 136 137 138 140 141 142 143 146 147 PI Ref Meter PI Fdback Meter PI Error Meter PI Output Meter Accel Time 1 Accel Time 2 Decel Time 1 Decel Time 2 S-Curve % Current Lmt Sel -100.00 % -100.00 % -100.00 % -[Maximum Freq] 0.1 Secs 0.1 Secs 0.1 Secs 0.
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 198 Load Frm Usr Set 199 Save To User Set 200 Reset Meters 201 Language 202 Voltage Class 203 209 Drive Checksum Drive Status 1 Minimum Value 0 Maximum Value Factory Default Ready User Set 1 User Set 2 User Set 3 Ready User Set 1 User Set 2 User Set 3 Ready MWh Elapsed Time Not Selected English Francais Espanol Italiano Deutsch Reserved Portugues Reserved Reserved Nederlands Low Voltage High Voltage 6
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 210 Drive Status 2 211 Drive Alarm 1 212 Drive Alarm 2 213 Speed Ref Source Minimum Value Maximum Value Factory Default Ready Active Running Jogging Stopping DC Braking Auto Tuning Unused AutoRst Ctdn AutoRst Act Curr Limit Bus Freq Reg Motor Overld DPI at 500 k Unused Unused Prechrg Actv UnderVoltage Power Loss Str At PwrUp Anlg in Loss IntDBRes OH Unused Drv OL Lvl 1 Drv OL Lvl 2 Decel Inhibt Unused Unus
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 214 Start Inhibits 215 Last Stop Source 216 Dig In Status 217 Dig Out Status 218 219 220 224 225 226 227 Drive Temp Drive OL Count Motor OL Count Fault Frequency Fault Amps Fault Bus Volts Status 1 @ Fault Minimum Value 0.0 0.0 0.0 0.0 0.0 Amps 0.
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 228 Status 2 @ Fault 229 Alarm 1 @ Fault 230 Alarm 2 @ Fault 234 235 236 237 238 Testpoint 1 Sel Testpoint 1 Data Testpoint 2 Sel Testpoint 2 Data Fault Config 1 240 Fault Clear 241 Fault Clear Mode 242 243 244 245 246 247 248 249 250 259 Power Up Marker Fault 1 Code Fault 1 Time Fault 2 Code Fault 2 Time Fault 3 Code Fault 3 Time Fault 4 Code Fault 4 Time Alarm Config 1 270 DPI Baud Rate 271 Drive L
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par 279 Parameter Name Minimum Value Maximum Value Factory Default DPI Port 1 DPI Port 2 DPI Port 3 Unused DPI Port 5 Digital In DPI Port 1 DPI Port 2 DPI Port 3 Unused DPI Port 5 1 1 1 X 1 1 1 1 1 X 1 Direction Mask 10 of 17 Programmed Value
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 280 Reference Mask 281 Accel Mask 282 Decel Mask 283 Fault Clr Mask 284 MOP Mask 285 Local Mask 288 Stop Owner 289 Start Owner 290 Jog Owner 291 Direction Owner 292 Reference Owner 293 Accel Owner Minimum Value Maximum Value Factory Default Digital In DPI Port 1 DPI Port 2 DPI Port 3 Unused DPI Port 5 Digital In DPI Port 1 DPI Port 2 DPI Port 3 Unused DPI Port 5 Digital In DPI Port 1 DPI Po
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 294 Decel Owner 295 Fault Clr Owner 296 MOP Owner 297 Local Owner 300 301 302 303 304 305 306 307 310 311 312 313 314 315 316 317 320 Data In A1 Data In A2 Data In B1 Data In B2 Data In C1 Data In C2 Data In D1 Data In D2 Data Out A1 Data Out A2 Data Out B1 Data Out B2 Data Out C1 Data Out C2 Data Out D1 Data Out D2 Anlg In Config 321 Anlg In Sqr Root 322 Analog In 1 Hi 323 Analog In 1 Lo Minimum Valu
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 324 Analog In 1 Loss 325 Analog In 2 Hi 326 Analog In 2 Lo 327 Analog In 2 Loss 341 342 Anlg Out Absolut Analog Out1 Sel 343 344 361 Analog Out1 Hi Analog Out1 Lo Digital In1 Sel Minimum Value 4.000 mA -10.0 V 0.0 4.000 mA -10.0V 0.0V 0.00 Volt 0.00 Volt Maximum Value Factory Default Disabled Fault Hold Input Set Input Lo Set Input Hi Goto Preset1 Hold OutFreq 20.000 mA +10.0 V 10.0 V 20.000 mA +10.
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 362 Digital In2 Sel 363 Digital In3 Sel Minimum Value Maximum Value Factory Default Not Used Enable Clear Faults Aux Fault Stop - CF Start Fwd/Reverse Run Run Forward Run Reverse Jog Jog Forward Jog Reverse Stop Mode B Bus Reg MD B Speed Sel 1 Speed Sel 2 Speed Sel 3 Auto/Manual Local Acc2 & Dec2 Accel 2 Decel 2 MOP Inc MOP Dec Excl Link PI Enable PI Hold PI Reset Not Used Enable Clear Faults Aux Fault Stop -
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 364 Digital In4 Sel 365 Digital In5 Sel Minimum Value Maximum Value Factory Default Not Used Enable Clear Faults Aux Fault Stop - CF Start Fwd/Reverse Run Run Forward Run Reverse Jog Jog Forward Jog Reverse Stop Mode B Bus Reg MD B Speed Sel 1 Speed Sel 2 Speed Sel 3 Auto/Manual Local Acc2 & Dec2 Accel 2 Decel 2 MOP Inc MOP Dec Excl Link PI Enable PI Hold PI Reset Not Used Enable Clear Faults Aux Fault Stop -
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 366 Digital In6 Sel 380 Digital Out1 Sel 381 382 383 Dig Out1 Level Dig Out1 OnTime Dig Out1 OffTime Minimum Value Maximum Value Factory Default Speed Set 3 0.0 0.00 Secs 0.
PowerFlex 70 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 384 Digital Out2 Sel 385 386 387 Dig Out2 Level Dig Out2 OnTime Dig Out2 OffTime Minimum Value Maximum Value Factory Default Run 0.0 0.00 Secs 0.
S.M.A.R.T.
Par Parameter Name 273 Drive Ramp Rslt 276 277 Factory Default Programmed Value Par Parameter Name Factory Default Read Only 1 Output Freq Read Only Logic Mask 1 2 Commanded Freq Read Only Start Mask 1 3 Output Current Read Only 278 Jog Mask 1 4 Torque Current Read Only 279 Direction Mask 1 5 Flux Current Read Only 280 Reference Mask 1 6 Output Voltage Read Only 281 Accel Mask 1 7 Output Power Read Only 282 Decel Mask 1 8 Output Powr Fctr Read Only 283
Par Parameter Name Factory Default Programmed Value Par Parameter Name Factory Default 104 Preset Speed 4 30.0 Hz 195 MOP Rate 1.0 Hz/s 105 Preset Speed 5 40.0 Hz 196 Param Access Lvl Basic 106 Preset Speed 6 50.0 Hz 197 Reset To Defalts Ready 107 Preset Speed 7 117 Trim In Select 118 Trim Out Select 119 Trim Hi 120 Trim Lo 121 Slip RPM @ FLA 122 60.0 Hz 198 Load Frm Usr Set Ready Analog In 2 199 Save To User Set Ready 0 200 Reset Meters 60.
PowerFlex 700 Parameter Record
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name Minimum Value 1 2 3 4 5 6 7 8 9 10 11 12 13 Output Freq Commanded Freq Output Current Torque Current Flux Current Output Voltage Output Power Output Powr Fctr Elapsed MWh Elapsed Run Time MOP Frequency DC Bus Voltage DC Bus Memory - [Maximum Freq] - [Maximum Speed] 0.0 Amps Drive Rating x -2 Drive Rating x -2 0.0 VAC 0.0 kW 0.00 0.0 MWh 0.0 Hrs - [Maximum Frequency] Based on Drive Rating Based on Drive Rating 0.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name Minimum Value 90 Speed Ref A Sel 91 92 93 Speed Ref A Hi Speed Ref A Lo Speed Ref B Sel - [Maximum Speed] - [Maximum Speed] + + 94 95 96 Speed Ref B Hi Speed Ref B Lo TB Man Ref Sel - [Maximum Speed] - [Maximum Speed] + + 97 98 100 101 102 103 104 105 106 107 TB Man Ref Hi TB Man Ref Lo Jog Speed Preset Speed 1 Preset Speed 2 Preset Speed 3 Preset Speed 4 Preset Speed 5 Preset Speed 6 Preset Speed 7 -
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 117 Trim In Select 118 Trim Out Select 119 120 121 122 123 124 Trim Hi Trim Lo Slip RPM @ FLA Slip Comp Gain Slip RPM Meter PI Configuration 125 PI Control 126 PI Reference Sel 127 PI Setpoint Minimum Value - [Maximum Speed] - [Maximum Speed] 0.0 RPM 1.0 0.0 RPM -100.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name Minimum Value 128 PI Feedback Sel 129 130 131 132 133 134 PI PI PI PI PI PI 135 136 137 138 140 141 142 143 146 147 PI Ref Meter PI Fdback Meter PI Error Meter PI Output Meter Accel Time 1 Accel Time 2 Decel Time 1 Decel Time 2 S-Curve % Current Lmt Sel -100.00 % -100.00 % -100.00 % -[Maximum Freq] 0.1 Secs 0.1 Secs 0.1 Secs 0.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name Minimum Value 156 Stop Mode B 157 DC Brk Lvl Sel 158 159 160 161 DC Brake Level DC Brake Time Bus Reg Ki Bus Reg Mode A 162 Bus Reg Mode B 163 DB Resistor Type 168 Start At PowerUp 169 Flying Start En 170 174 175 184 Flying StartGain Auto Rstrt Tries Auto Rstrt Delay Power Loss Mode 20 0 0.5 Secs 185 190 Power Loss Time Direction Mode 0.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 209 Drive Status 1 210 Drive Status 2 211 Drive Alarm 1 Minimum Value Maximum Value Factory Default Ready Active Command Dir Actual Dir Accelerating Decelerating Alarm Faulted At Speed Local ID 0 Local ID 1 Local ID 2 Spd Ref ID 0 Spd Ref ID 1 Spd Ref ID 2 Spd Ref ID 3 Ready Active Running Jogging Stopping DC Braking Auto Tuning Unused AutoRst Ctdn AutoRst Act Curr Limit Bus Freq Reg Motor Overld DPI at 500
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 212 Drive Alarm 2 213 Speed Ref Source 214 Start Inhibits 215 Last Stop Source 216 Dig In Status 217 Dig Out Status 218 219 220 224 225 226 Drive Temp Drive OL Count Motor OL Count Fault Frequency Fault Amps Fault Bus Volts Minimum Value Maximum Value Factory Default 0 0 0 0 0 0 0 0 0 0 0 Read Only 0.0 0.0 0.0 0.0 0.0 Amps 0.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 227 Status 1 @ Fault 228 Status 2 @ Fault 229 Alarm 1 @ Fault Minimum Value Maximum Value Factory Default Ready Active Command Dir Actual Dir Accelerating Decelerating Alarm Faulted At Speed Local ID 0 Local ID 1 Local ID 2 Spd Ref ID 0 Spd Ref ID 1 Spd Ref ID 2 Spd Ref ID 3 Ready Active Running Jogging Stopping DC Braking AutoTuning Unused AutoRst Ctdn Auto Rst Act Curr Limit Bus Freq Reg Motor Overld DPI
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 230 Alarm 2 @ Fault 234 235 236 237 238 Testpoint 1 Sel Testpoint 1 Data Testpoint 2 Sel Testpoint 2 Data Fault Config 1 240 Fault Clear 241 Fault Clear Mode 242 243 244 245 246 247 248 249 250 259 Power Up Marker Fault 1 Code Fault 1 Time Fault 2 Code Fault 2 Time Fault 3 Code Fault 3 Time Fault 4 Code Fault 4 Time Alarm Config 1 270 DPI Baud Rate 271 Drive Logic Rslt 272 273 276 Drive Ref Rslt Drive
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 283 Fault Clr Mask 284 MOP Mask Minimum Value Maximum Value Factory Default DPI Port 3 Unused DPI Port 5 Digital In DPI Port 1 DPI Port 2 DPI Port 3 Unused DPI Port 5 Digital In DPI Port 1 DPI Port 2 DPI Port 3 Unused DPI Port 5 1 X 1 1 1 1 1 X 1 1 1 1 1 X 1 10 of 17 Programmed Value
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 285 Local Mask 288 Stop Owner 289 Start Owner 290 Jog Owner 291 Direction Owner 292 Reference Owner 293 Accel Owner 294 Decel Owner 295 Fault Clr Owner 296 MOP Owner 297 Local Owner 300 301 302 303 304 305 306 307 310 311 312 313 314 315 316 317 320 Data In A1 Data In A2 Data In B1 Data In B2 Data In C1 Data In C2 Data In D1 Data In D2 Data Out A1 Data Out A2 Data Out B1 Data Out B2 Data Out C
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par 341 Parameter Name Anlg Out Absolut Minimum Value Maximum Value Factory Default Goto Preset1 Hold OutFreq Analog Out1 1 12 of 17 Programmed Value
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 342 Analog Out1 Sel 343 344 361 Analog Out1 Hi Analog Out1 Lo Digital In1 Sel 362 Digital In2 Sel Minimum Value 0.00 Volt 0.00 Volt Maximum Value Factory Default Output Freq Command Freq Output Amps Torque Amps Flux Amps Output Power Output Volts DC Bus Volts PI Reference PI Feedback PI Error PI Outout %Motor OL %Drive OL 10.00 Volt 10.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par 363 Parameter Name Digital In3 Sel Minimum Value Maximum Value Factory Default Not Used Enable Clear Faults Aux Fault Stop - CF Start Fwd/Reverse Run Run Forward Run Reverse Jog Jog Forward Jog Reverse Stop Mode B Bus Reg MD B Speed Sel 1 Speed Sel 2 Speed Sel 3 Auto/Manual Local Acc2 & Dec2 Accel 2 Decel 2 MOP Inc MOP Dec Excl Link PI Enable PI Hold PI Reset Auto/Manual 14 of 17 Programmed Value
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 364 Digital In4 Sel 365 Digital In5 Sel Minimum Value Maximum Value Factory Default Not Used Enable Clear Faults Aux Fault Stop - CF Start Fwd/Reverse Run Run Forward Run Reverse Jog Jog Forward Jog Reverse Stop Mode B Bus Reg MD B Speed Sel 1 Speed Sel 2 Speed Sel 3 Auto/Manual Local Acc2 & Dec2 Accel 2 Decel 2 MOP Inc MOP Dec Excl Link PI Enable PI Hold PI Reset Not Used Enable Clear Faults Aux Fault Stop -
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 366 Digital In6 Sel 380 Digital Out1 Sel 381 382 383 Dig Out1 Level Dig Out1 OnTime Dig Out1 OffTime Minimum Value Maximum Value Factory Default Speed Set 3 0.0 0.00 Secs 0.
PowerFlex 700 Parameter Record Machine # Date programmed Drive Serial # Par Parameter Name 384 Digital Out2 Sel 385 386 387 Dig Out2 Level Dig Out2 OnTime Dig Out2 OffTime Minimum Value Maximum Value Factory Default Run 0.0 0.00 Secs 0.