Manual
180 Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Appendix A Specifications
Table 13 - 540 Volt DC Input Frames 9…14 Drive Protection Devices
20xF1K0 13 1000 – 1038 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
– 900 927 1200 (1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M6466
(5)
2700 1200
20xF1K1 13 1100 – 1189 1500 (1 per phs)
750 (2 per phs)
2600 1500 (1 per phs)
750 (2 per phs)
3500 170M6466
(5)
3500 1500
– 1000 1038 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
20xF1K5 14 1500 – 1511 1900 (1 per phs)
650 (3 per phs)
3300 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
– 1300 1310 1700 (1 per phs)
575 (3 per phs)
2900 1700 (1 per phs)
575 (3 per phs)
3900 170M6466 3900 1700
20xF1K9
(2)
14 1800 – 1914 2400 (1 per phs)
800 (3 per phs)
4200 2400 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
– 1500 1511 1900 (1 per phs)
650 (3 per phs)
3200 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
20xF2K2
(2)
14 2000 – 2267 2900 (1 per phs)
950 (3 per phs)
5000 2900 (1 per phs)
950 (3 per phs)
6700 170M6466 6700 2900
– 1800 1914 2400 (1 per phs)
800 (3 per phs)
4200 2400 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
(1) 20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2) Not available with 700S Control.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection.
(5) These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6) Inverse time breaker. Ratings shown are maximum.
(7) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not
to exceed 1300% FLA.
Drive Catalog
Number
Frame
kW Rating Input
Ratings
Dual Element Time Delay Fuse Non-Time Delay Fuse Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND HD Amps Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.
Drive Catalog Number Frame kW Rating DC Input Ratings Fuse Bussmann Style Fuse
ND HD Amps
20xH261 9 132 - 307 500 170M6608
- 110 241 500 170M6608
20xH300 9 160 - 353 630 170M6610
- 132 288 630 170M6610
20xH385 10 200 - 453 700 170M6611
- 160 353 700 170M6611
20xH460 10 250 - 541 900 170M6613
- 200 453 900 170M6613
20xH500 10 250 - 589 500 (2 per phs) 170M6608
- 250 494 500 (2 per phs) 170M6608
20xH590 11 315 - 695 550 (2 per phs) 170M6609
- 250 612 550 (2 per phs) 170M6609
20xH650 11 355 - 765 630 (2 per phs) 170M6610
- 315 695 630 (2 per phs) 170M6610
20xH730 11 400 - 859 700 (2 per phs) 170M6611
- 355 765 700 (2 per phs) 170M6611
20xH820 12 450 - 965 700 (2 per phs) 170M6611
- 400 859 700 (2 per phs) 170M6611
20xH920 12 500 - 1083 550 (3 per phs) 170M6609
- 450 965 550 (3 per phs) 170M6609
20xH1K0 12 560 - 1213 630 (3 per phs) 170M6610
- 500 1083 630 (3 per phs) 170M6610
20xH1K1 13 630 - 1354 2400 170M7107
- 560 1213 2400 170M7107
20xH1K3 13 710 - 1530 2400 170M7107
- 630 1354 2400 170M7107