Manual
64 Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 5 Frame 9 Mechanical Installation
Minimum Mounting
Clearances
Operating Temperatures
Frame 9 drives require a minimum of 1300 m
3
/h (765 cfm) of cooling air.
Nameplate Location
See Figure 15 on page 65.
400.0 mm
(15.75 in.)
80.0 mm
(3.2 in.)
50.0 mm
(1.97 in.)
350.0 mm
(13.8 in.)
400.0 mm
(15.75 in.)
350.0 mm
(13.8 in.)
50.0 mm
(1.97 in.)
See Figure 15 on page 65 for detailed dimension information.
PowerFlex Drive Voltage Class Amp Rating Surrounding Air Temperature
Normal Duty Heavy Duty
700H All All 0…40° C
(32…104° F)
0…50° C
(32 to 122° F)
700S 400/480V AC
(540/650V DC)
All 0…40° C
(32…104° F)
0…40° C
(32…104° F)
600/690V AC
(810/932V DC)
170 0…40° C
(32…104° F)
0…40° C
(32…104° F)
208 0…35° C
(32…95° F)
0…40° C
(32…104° F)