B-2 WIM Parameters
04 [Drive Addr Act]
Displays the node address of the drive that the WIM is
communicating with when the WIM is set to RTU
Master mode using Parameter 01 - [Adapter Cfg].
Default: 1
Minimum: 1
Maximum 247
Type: Read Only
05 [Security Mode]
Enables/disables the security mode for the WIM, which
prevents accessing its parameters and the connected
drive for configuration.
Default: 0
Values: 0 = PIN Not Req’d
1 = PIN Required
Type: Read/Write
Reset Required: Yes
06 [Security PIN]
Sets the PIN number to access WIM parameters for
configuration when Parameter 05 - [Security Mode] is
set to 1 = PIN Required. See Page 3-25
for details.
Default: 0
Minimum: 0
Maximum: 9999
Type: Read/Write
Reset Required: Yes
07 [Comm Flt Action]
Sets the action that the WIM and drive will take if the
WIM detects that DF1 serial communications are
disrupted. This setting is effective only if control I/O is
transmitted through the WIM.
Default: 0 = Fault
Values: 0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
Type: Read/Write
Reset Required: No
08 [Reset Module]
No action if set to “Ready.” Resets the WIM if set to
“Reset Module.” Restores the WIM to its factory default
settings if set to “Set Defaults.” This parameter is a
command. It will be set to “0 = Ready” after the
command has been performed.
Default: 0 = Ready
Values: 0 = Ready
1 = Reset Module
2 = Set Defaults
Type: Read/Write
Reset Required: No
09 [Clear DF1 Counts]
No action if set to “Ready.” Resets the DF1 statistical
parameters 10 and 11 to 0 if set to “1 = Clear Counts.
This parameter is a command. It will be reset to
“0 = Ready” after a “Clear Counts” command has been
performed.
Default: 0 = Ready
Values: 0 = Ready
1 = Clear Counts
Type: Read/Write
Reset Required: No
10 [DF1 Packets Sent]
Displays the number of DF1 packets sent by the WIM.
The value of this parameter is normally approximately
equal to the Parameter 11 - [DFI Packets Rcvd] value.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
11 [DF1 Packets Rcvd]
Displays the number of DF1 packets received by the
WIM. The value of this parameter is normally
approximately equal to the Parameter 10 - [DFI
Packets Sent] value.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
No. Name and Description Details
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 07 -
[Comm Flt Action] lets you determine the action of the WIM and connected
drive if communications are disrupted. By default, this parameter faults the drive.
You can set this parameter so that the drive continues to run. Precautions
should be taken to ensure that the setting of this parameter does not create a
risk of injury or equipment damage. When commissioning the drive, verify that
your system responds correctly to various situations (for example, a disconnect
cable).
!
ATTENTION: Risk of injury or equipment damage exists.The drive will fault
when you remove or reset the WIM. Determine how the drive will respond before
removing or resetting the WIM.