Quick Start FRN 6.xx User Manual
Español-10
Parámetros de Grupo Avanzados
No. Parámetro Mín/Máx Pantalla /Opciones
Valor
Predeterminado
A051
A052
[Sel. ent digt 1]
Terminales de E/S 05
[Sel. ent digt 2]
Terminal de E/S 06
0/26 0 = “No se usa”
1 = “Acel/Decel 2”
2 = “Avan/impuls”
3 = “Fallo Aux”
4 = “Frec presel”
5 = “Local”
6 = “Puerto Com”
7 = “Borrar Fallo”
8 = “ParoRamp,CF”
9 = “ParInerc,CF”
10 = “ParInjCC,CF”
11 = “ImpulsAvance”
12 = “ImpulsRetroc”
13 = “EntCtrl10V”
14 = “EntCtrl20mA”
26 = “Inver Anlg”
4
A055 [Sel. Sal. Pulsos] 0/21 0 = “Listo/Fallo”
1 = “EnFrecuencia”
2 = “MotorMarcha”
3 = “Retroceso”
4 = “Sobrcarg mtr”
5 = “Reg Ramp”
6 = “Sobre Frec”
7 = “Sobre Cte”
8 = “Sobre V CC”
9 = “AgotReintent”
10 = “Sobre V Anlg”
20 = “ContParám”
21 = “Fallo no rec”
0
A056 [Nivel Sal Pulsos] 0.0/9999 0.1 0.0
A067 [Tiempo acel. 2] 0.0/600.0 segs 0.1 segs 20.0 segs
A068 [Tiempo decel. 2] 0.1/600.0 segs 0.1 segs 20.0 segs
A069 [Frec Interna] 0.0/240.0 Hz 0.1 Hz 60.0 Hz
A070
A071
A072
A073
[Frec presel 0]
( (1)
[Frec presel 1]
[Frec presel 2]
[Frec presel 3]
0.0/240.0 Hz 0.1 Hz 0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
(1)
Para activar [Frec presel 0] establezca P038 [Referencia Veloc] en la opción 4.
A078 [Frecuencia test] 0.0/[Frecuencia Máx.] 0.1 Hz 10.0 Hz
A079 [Impulsos Ace/Dec] 0.1/600.0 segs 0.1 segs 10.0 segs
A080 [Tiempo freno CC] 0.0/90.0 segs 0.1 segs 0.0 segs
A081 [Nivel freno CC] 0.0/(Intens. Var × 1.8) 0.1 Amps Amps × 0.05
A082 [Sel resisten FD] 0/99 0 = Inhabilitado
1 = Res RA Norml
2 = SinProtecc
3-99 = CiclTrab %
0
A083 [% curva-S] 0/100% 1% 0% (Inhabilitado)
A084 [Refuer. arranque] 1/14 Ajustes en % de tensión base. 8
7 (Variadores
de 5 HP)
Par Variable Par Constante
1 = “30.0, VT” 5 = “0.0, no IR” 10 = “10.0, CT”
2 = “35.0, VT” 6 = “0.0” 11 = “12.5, CT”
3 = “40.0, VT” 7 = “2.5, CT” 12 = “15.0, CT”
4 = “45.0, VT” 8 = “5.0, CT” 13 = “17.5, CT”
9 = “7.5, CT” 14 = “20.0, CT”
A088 [Tensión máxima] 20/Volts nomin var. 1 V CA Volts nomin var.
A089 [Lím. Corriente] 0/(Intens. Var × 1.8) 0.1 Amps Amps × 1.5
A090 [Selec. SC Motor] 0/2 0 = “NoDesclasif” 1 = “DesclasifMín”
2 = “DesclasifMáx”
0
A091 [Frecuencia PWM] 2.0/16.0 kHz 0.1 kHz 4.0 kHz
A092 [Int. rearme auto] 0/9 1 0
A093 [Retrd reinic aut] 0.0/300.0 segs 0.1 segs 1.0 segs
A094 [Inic al encender] 0/1 0 = “Inhabilitado” 1 = “Habilitado” 0
A095 [Inver Deshab.] 0/1 0 = “Rev Habilit” 1 = “Rev Inhabil” 0
A096 [Act. mrch. Vuelo] 0/1 0 = “Inhabilitado” 1 = “Habilitado” 0
A097 [Compensación] 0/3 0 = “Inhabilitado”
1 = “Eléctrico”
2 = “Mecánico”
3 = “Ambos”
1
A098 [Disparo Corr. SW] 0.0/(Intens. Var × 2) 0.1 Amps 0.0 = (Inhabilitado)
A099 [Factor Proceso] 0.1/999.9 0.1 30.0
A100 [Borrar fallo] 0/2 0 = “Listo/Inactv” 1 = “Restab fallo”
2 = “BorrarBuffer”
0
A101 [Bloqueo Programa] 0/1 0 = “Desbloqueado” 1 = “Bloqueado” 0
A102 [Sel pto. Prueba] 0/FFFF 1 Hex 400
Estado de Entrada de Ent.
Digital 1 (Terminal de E/S 05)
Estado de Entrada de Ent.
Digital 2 (Terminal de E/S 06)
Fuente de
Frecuencia
Parámetro Acel./Decel. utilizado
(2)
0 0 [Frec presel 0] [Tiempo acel. 1] / [Tiempo decel. 1]
1 0 [Frec presel 1] [Tiempo acel. 1] / [Tiempo decel. 1]
0 1 [Frec presel 2] [Tiempo acel. 2] / [Tiempo decel. 2]
1 1 [Frec presel 3] [Tiempo acel. 2] / [Tiempo decel. 2]
(2)
Cuando una entrada digital se establece en “Acel/Decel 2” y la entrada está activa, dicha entrada anula los ajustes en
esta tabla.
Consulte el Manual del Usuario del PowerFlex 4 para más información sobre parámetros.