Quick Start FRN 6.xx User Manual
Nederlands-10
Uitgebreide-groepparameters
Nr. Parameter Min/Max Display/Opties Default
A051
A052
[Sel digit ing 1]
I/O aansluit-
terminal 05
[Sel digit ing 2]
I/O aansluit-
terminal 06
0/26 0 = “Niet gebruikt”
1 = “Acc 2 & dec 2”
2 = “Joggen”
3 = “Fout aux”
4 = “Preset freq”
5 = “Lokaal”
6 = “Comm.poort”
7 = “Fout wissen”
8 = “Ac/dcStpFtws”
9 = “VrlpStp ftws”
10 = “DCInjStpFtws”
11 = “Vooruit jog”
12 = “Achtruit jog”
13 = “Reg 10 V in”
14 = “Reg 20 mA in”
26 = “Anal invert”
4
A055 [Sel relais-uitg] 0/21 0 = “Gereed/fout”
1 = “Op freq”
2 = “Mtr in bedrf”
3 = “Achteruit”
4 = “Motoroverbel”
5 = “Reg acc/dec”
6 = “Te hoge freq”
7 = “Te hg stroom”
8 = “Te hoge DC V”
9 = “Pogingen op”
10 = “Te hg anal V”
20 = “Param reg”
21 = “Nt-hrst fout”
0
A056 [Niv relais-uitg] 0,0/9999 0,1 0,0
A067 [Accel.tijd 2] 0,0/600,0 sec 0,1 sec 20,0 sec
A068 [Decel.tijd 2] 0,1/600,0 sec 0,1 sec 20,0 sec
A069 [Interne freq] 0,0/240,0 Hz 0,1 Hz 60,0 Hz
A070
A071
A072
A073
[Preset freq 0]
(1)
[Preset freq 1]
[Preset freq 2]
[Preset freq 3]
0,0/240,0 Hz 0,1 Hz 0,0 Hz
5,0 Hz
10,0 Hz
20,0 Hz
(1)
Om [Preset freq 0] te activeren stelt u P038 [Snelheidsref] in op optie 4.
A078 [Jog freq] 0,0/[Max frequentie] 0,1 Hz 10,0 Hz
A079 [Jog Accel/Decel] 0,1/600,0 sec 0,1 sec 10,0 sec
A080 [DC remtijd] 0,0/90,0 sec 0,1 sec 0,0 sec
A081 [DC remniveau] 0,0/(A van drive × 1,8) 0,1 A A × 0,05
A082 [Sel DB weerstand] 0/99 0 = Uit
1 = Norm RA wrst
2 = Gn bescherm
3-99 = % van cyclus
0
A083 [% S-kromme] 0/100% 1% 0% (Uit)
A084 [Start boost] 1/14 Instellingen in % van basisspanning. 8
7 (drives van
3,75 kW)
Variabel koppel
Constant koppel
1 = “30,0; VT” 5 = “0,0; geen IR” 10 = “10,0; CT”
2 = “35,0; VT” 6 = “0,0” 11 = “12,5; CT”
3 = “40,0; VT” 7 = “2,5; CT” 12 = “15,0; CT”
4 = “45,0; VT” 8 = “5,0; CT” 13 = “17,5; CT”
9 = “7,5; CT” 14 = “20,0; CT”
A088 [Max spanning] 20/Nominale V 1 VAC Nominale V
A089 [Stroomgrens 1] 0/(A van drive × 1,8) 0,1 A A × 1,5
A090 [Sel mtr overbel] 0/2 0 = “Geen derate” 1 = “Min derate”
2 = “Max derate”
0
A091 [PWM frequentie] 2,0/16,0 kHz 0,1 kHz 4,0 kHz
A092 [Poging aut hstrt] 0/9 1 0
A093 [Vertr aut hstrt] 0,0/300,0 sec 0,1 sec 1,0 sec
A094 [Start bij powerup] 0/1 0 = “Uit” 1 = "Vrijgegeven” 0
A095 [Achteruit uit] 0/1 0 = “A.uit vrijg” 1 = “A.uit uit” 0
A096 [Vlg strt vrijgeg] 0/1 0 = “Uit” 1 = “Vrijgegeven” 0
A097 [Compensatie] 0/3 0 = “Uit”
1 = “Elektrisch”
2 = “Mechanisch”
3 = “Beide”
1
A098 [Uitsch stroom SW] 0,0/(A van drive × 2) 0,1 A 0,0 (Uit)
A099 [Procesfactor] 0,1/999,9 0,1 30,0
A100 [Fout wissen] 0/2 0 = “Gereed/Idle” 1 = “Fout reset”
2 = “Buffer wis”
0
A101 [Program vergrend] 0/1 0 = “Ontgrendeld” 1 = “Vergrendeld” 0
A102 [Sel testpunt] 0/FFFF 1 Hex 400
Ingangstoestand van digitale ing 1
(I/O aansluitterminal 05)
Ingangstoestand van digitale ing 2
(I/O aansluitterminal 06)
Frequentiebron Gebruikte parameter Accel/decel
(2)
0 0 [Preset freq 0] [Accel.tijd 1] / [Decel.tijd 1]
1 0 [Preset freq 1] [Accel.tijd 1] / [Decel.tijd 1]
0 1 [Preset freq 2] [Accel.tijd 2] / [Decel.tijd 2]
1 1 [Preset freq 3] [Accel.tijd 2] / [Decel.tijd 2]
(2)
Wanneer een digitale ingang op “Accel 2 en Decel 2” wordt ingesteld, en de ingang actief is, gaat de
ingang aan de instellingen in deze tabel voorbij.
Zie de Gebruikershandleiding van de PowerFlex 4 voor meer informatie over parameters.