User Manual FRN 6.xx Manual

Programming and Parameters 3-23
Advanced Program Group (continued)
A100 [Fault Clear]
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options 0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer” (Parameters d007
-d009 [Fault x Code])
A101 [Program Lock]
Protects parameters against change by unauthorized personnel.
Options 0 “Unlocked” (Default)
1 “Locked”
A102 [Testpoint Sel]
Used by Rockwell Automation field service personnel.
Values Default 400
Min/Max: 0/FFFF
Display: 1 Hex
A103 [Comm Data Rate] Related Parameter(s): d015
Sets the serial port rate for the RS485 (DSI) port.
Important: Power to drive must be cycled before any changes will affect drive operation.
Options 0 “1200”
1 “2400”
2 “4800”
3 “9600” (Default)
4 “19.2K”
5 “38.4K”
A104 [Comm Node Addr] Related Parameter(s): d015
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important: Power to drive must be cycled before any changes will affect drive operation.
Values Default 100
Min/Max: 1/247
Display: 1