Specifications
The following tables provide specifications for the PowerFlex 40 configured AC
drives.
Specifications Tables
Table 6 - Standard Configured Drive Products
Table 7 - Standard PowerFlex 40 Drives
Input/Output Ratings Output Frequency: 0…400 Hz (Programmable)
Efficiency: 97.5% (Typical)
Approvals
Fuses and Power
Disconnecting Means
140M Motor Circuit Protector: Provides branch circuit protection, see Table 1 on page 12
for short circuit withstand rating, on grounded wye
neutral distribution systems only
194R Fused Disconnect: Provides branch circuit protection, 200 kA short circuit withstand, Class J fuses
Protective Features Over Voltage: 480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
Under Voltage: 480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
Environment Ambient Operating Temperature, NEMA 4/12, 4X (IP66): –10 to 40 degrees C (14 to 104 degrees F)
(1)
Cooling Method: Fan (All drive ratings)
Control Carrier Frequency: 2…4 kHz. Drive rating and heat calculations are based on 4 kHz.
(1) The design of the PowerFlex 40 Standard Configured Drive NEMA 4/12 and 4X packages support indoor and outdoor applications that are not in direct sunlight. When optional Door Mounted HIM is
supplied, enclosure is rated for indoor use only.
Digital Control Inputs
(Input Current = 6 mA)
SRC (Source) Mode: 18…24 Volts = ON; 0…6 Volts = OFF
SNK (Sink) Mode: 0…6 Volts = ON; 18…24 Volts = OFF
Analog Control Inputs 4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1…10k ohms, 2 Watt minimum
Control Output Programmable Output (form C relay)
Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Opto Outputs
30V DC, 50 mA
Non-inductive
Analog Output (10-bit)
0-10V, 1k ohm Min.
Fuses and Circuit Breakers Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Recommended Circuit Breakers: HMCP circuit breaker or equivalent.
Protective Features Motor Protection: I
2
t overload protection – 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent: 200% hardware limit, 300% instantaneous fault
Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs