Quick Start - FRN 1.xx - 3.xx Instruction Manual
English-4
Refer to the PowerFlex 40P User Manual for details on how to comply
with the Low Voltage (LV) and Electromagnetic Compatibility (EMC)
Directives.
Drive Ratings
CE Conformity
Specifications, Fuses and Circuit Breakers
Catalog
Number
(1)
Output Ratings Input Ratings Branch Circuit Protection
kW (HP) Amps
Voltage
Range kVA Amps Fuses
140M Motor
Protectors Contactors
200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output
22D-B2P3 0.4 (0.5) 2.3 180-264 1.15 2.5 6 140M-C2E-B40 100-C07
22D-B5P0 0.75 (1.0) 5.0 180-264 2.45 5.7 10 140M-C2E-C10 100-C09
22D-B8P0 1.5 (2.0) 8.0 180-264 4.0 9.5 15 140M-C2E-C16 100-C12
22D-B012 2.2 (3.0) 12.0 180-264 5.5 15.5 25 140M-C2E-C16 100-C23
22D-B017 3.7 (5.0) 17.5 180-264 8.6 21.0 30 140M-F8E-C25 100-C23
22D-B024 5.5 (7.5) 24.0 180-264 11.8 26.1 40 140M-F8E-C32 100-C37
22D-B033 7.5 (10.0) 33.0 180-264 16.3 34.6 60 140M-G8E-C45 100-C60
380 - 480V AC (±10%) – 3-Phase Input, 0 - 460V 3-Phase Output
22D-D1P4 0.4 (0.5) 1.4 342-528 1.4 1.8 3 140M-C2E-B25 100-C07
22D-D2P3 0.75 (1.0) 2.3 342-528 2.3 3.2 6 140M-C2E-B40 100-C07
22D-D4P0 1.5 (2.0) 4.0 342-528 4.0 5.7 10 140M-C2E-B63 100-C09
22D-D6P0 2.2 (3.0) 6.0 342-528 5.9 7.5 15 140M-C2E-C10 100-C09
22D-D010 4.0 (5.0) 10.5 342-528 10.3 13.0 20 140M-C2E-C16 100-C23
22D-D012 5.5 (7.5) 12.0 342-528 11.8 14.2 25 140M-D8E-C20 100-C23
22D-D017 7.5 (10.0) 17.0 342-528 16.8 18.4 30 140M-D8E-C20 100-C23
22D-D024 11.0 (15.0) 24.0 342-528 23.4 26.0 50 140M-F8E-C32 100-C43
460 - 600V AC (±10%) – 3-Phase Input, 0 - 575V 3-Phase Output
22D-E1P7 0.75 (1.0) 1.7 414-660 2.1 2.3 6 140M-C2E-B25 100-C09
22D-E3P0 1.5 (2.0) 3.0 414-660 3.65 3.8 6 140M-C2E-B40 100-C09
22D-E4P2 2.2 (3.0) 4.2 414-660 5.2 5.3 10 140M-C2E-B63 100-C09
22D-E6P6 4.0 (5.0) 6.6 414-660 8.1 8.3 15 140M-C2E-C10 100-C09
22D-E9P9 5.5 (7.5) 9.9 414-660 12.1 11.2 20 140M-C2E-C16 100-C16
22D-E012 7.5 (10.0) 12.2 414-660 14.9 13.7 25 140M-C2E-C16 100-C23
22D-E019 11.0 (15.0) 19.0 414-660 23.1 24.1 40 140M-D8E-C25 100-C30
(1)
Ratings apply to all drive types; Panel Mount (N104), Flange Mount (F104), and Plate Drive
(H204).