3-4 Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Display Group (continued)
d006 [Drive Status] Related Parameter(s): A434
Present operating condition of the drive.
Values Default Read Only
Min/Max: 0/1
Display: 1
1 = Condition True, 0 = Condition False
Running Bit 0
Forward Bit 1
Accelerating Bit 2
Decelerating Bit 3
d007 [Fault 1 Code]
d008 [Fault 2 Code]
d009 [Fault 3 Code]
A code that represents a drive fault. The codes will appear in these parameters in the order they occur
(
d007 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once.
Refer to
Chapter 4 for fault code descriptions.
Values Default Read Only
Min/Max: F2/F122
Display: F1
d010 [Process Display] Related Parameter(s): d001, A440, A438, A439
32 bit parameter.
The output frequency scaled by
A440 [Process Factor] or by A438 [Process Time Lo] and A439
[Process Time Hi].
Values Default Read Only
Min/Max: 0.00/9999
Display: 0.01 – 1
32
Output
Freq
Process
Factor
Process
Display
=
x