User Manual FRN 1.xx - 2.xx Instruction Manual

Programming and Parameters 3-7
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Display Group (continued)
d018 [Elapsed Run Time]
Accumulated time drive is outputting power. Time is displayed in 10-hour increments.
Values Default Read Only
Min/Max: 0/9999 Hrs
Display: 1 (= 10 Hrs)
d019 [Testpoint Data] Related Parameter(s): A459
The present value of the function selected in A459 [Testpoint Sel].
Values Default Read Only
Min/Max: 0/FFFF
Display: 1 Hex
d020 [Analog In 0-10V] Related Parameter(s): t211, t212
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).
Values Default Read Only
Min/Max: 0.0/100.0%
Display: 0.1%
d021 [Analog In 4-20mA] Related Parameter(s): t213, t214
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
Values Default Read Only
Min/Max: 0.0/100.0%
Display: 0.1%
d022 [Drive Temp]
Present operating temperature of the drive power section.
Values Default Read Only
Min/Max: 0/120 degC
Display: 1 degC