User Manual FRN 1.xx - 2.xx Instruction Manual
3-8 Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Basic Program Group
P101 [Motor NP Volts] Related Parameter(s): d004, A453
Stop drive before changing this parameter.
Set to the motor nameplate rated voltage.
Values Default Based on Drive Rating
Min/Max: 20/Drive Rated Voltage
Display: 1 VAC
P102 [Motor NP Hertz] Related Parameter(s): A453, A444
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values Default 60 Hz
Min/Max: 10/400 Hz
Display: 1 Hz
P103 [Motor OL Current] Related Parameter(s): P111, t221, A441, A444, A448, A437
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60
sec
onds or 200% for 3 seconds.
Values Default Based on Drive Rating
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
P104 [Minimum Freq] Related Parameter(s): d001, d002, d013, P105, t211, t213, A438
Sets the lowest frequency the drive will output continuously.
Values Default 0.0 Hz
Min/Max: 0.0/400.0 Hz
Display: 0.1 Hz
P105 [Maximum Freq]
Related Parameter(s): d001, d002, d013, P104, A404,
t212, t214, A438
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values Default 60 Hz
Min/Max: 0/400 Hz
Display: 1 Hz