Installation Owner manual

Bulletin 500F Contactor Installation
(Cat 500F-AOD930; 500F-BOD930; 500F-COD930; 500F-DOD930; 500F-EOD930)
Short Circuit Current Ratings
PN-68120
DIR 10000093749 (Version 02)
Printed in U.S.A.
To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free
from contaminants.
Avant le montage et la mise en service, couper l'alimentation secteur pour éviter toute décharge. Prévoir une mise en coffret ou
armoire appropriée. Protéger le produit contre les environnements agressifs.
Desconéctese de la corriente eléctrica, antes de la instalación o del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una
caja apropiada. Manténgalo libre de contaminantes.
NOTE: For NEMA Sizes 0, 1 and 2, if space is critical, the overload relay mounting plate can be detached from the
contactor mounting plate by removing the (2) #8-32 screws.
WARNING
AVERTISSEMENT
WARNUNG
35 lb-in
.sM
Size 2
140 lb-in
.sM
Size 3
200 lb-in
.sM
Size 4
Standard Fault Short Circuit Ratings
Contactor/Starter
(
notes a & b
)
NEMA
Sizes
Max. Voltage (V)
SCCR
(
kA
)
500-**/500F-**/509-** 0,1,2 & 3 240 1Ø, 600 3Ø 5
500-E*/500F-E*/509-E* 4 600 3Ø 10
Contactors and Starters Protected by Inverse-Time Circuit Breakers
Contactor/Starter
(note b)
NEMA
Size
Max.
Voltage (V)
(3Ø unless
noted)
Max. A-B Bul.
140U Circuit
Breaker
(note c)
(Starters Only)
SCCR
(kA)
Max. Cutler-Hammer
FDB/LFD Circuit
Breaker / Current
Limiter Combination
SCCR (kA)
240 140U-H_C3-C40 25 FDB 3025/LFD 3070R
100
(
1Ø & 3Ø
)
480 140U-H_C3-C40 25 FDB 3025/LFD 3070R 100
600 140U-H_C3-C20 18
240 140U-H_C3-C40 25 FDB 3050/LFD 3070R
100
(
1Ø & 3Ø
)
480 140U-H_C3-C40 25 FDB 3035/LFD 3070R 100
600 140U-H_C3-C20 18
480 140U-H_C3-C70 25 FDB 3100/LFD 3150R
100
(
240V Max
)
600 140U-H_C3-C50 18
240 140U-H_C3-D12 25 FDB 3150/LFD 3150R 100
480 140U-H_C3-D12 25 FDB 3125/LFD 3150R 100
600 140U-H_C3-D10 18 FDB 3100/LFD 3150R 100
480 140U-H_C3-D12 25 FDB 3150/LFD 3150R 100
600 140U-H_C3-D12 18 FDB 3150/LFD 3150R 100
480 140U-J_D3-D20 25
600 140U-J_D3-D17 18
500-E*/500F-E*/509-E* 4
500-E*/500F-E*/509-E* 4
500-A*/500F-A*/509-A*
0
(note d)
500-B*/500F-B*/509-B*
500-D*/500F-D*/509-D* 3
1
500-C*/500F-C*/509-C* 2
High Fault Short Circuit Ratings
Contactors and Starters Protected by Fuses
Class R Class J
240 1Ø & 3Ø 30 30 100
600 30 30 100
240 1Ø & 3Ø 60 100 100
600 30 50 100
240 1Ø & 3Ø 100 200 100
600 60 100 100
240 200 350 100
600 100 200 100
240 300 500 100
600 200 400 100
500-E*/500F-E*/509-E* 4
500-C*/500F-C*/509-C* 2
500-D*/500F-D*/509-D* 3
SCCR
(kA)
500-A*/500F-A*/509-A* 0
500-B*/500F-B*/509-B* 1
Contactor/Starter
(note b)
NEMA
Size
Max. Voltage (V)
(3Ø unless noted)
Max. Fuse Rating
High Fault Short Circuit Ratings
Contactors and Starters Protected by Instantaneous-Trip Circuit Breakers
Contactor/Starter
(note b)
NEMA
Size
Max.
Voltage (V)
(3Ø unless
noted)
Max. A-B Bul.
140M Circuit
Breaker
SCCR
(kA)
480 140M-I8P-C15 42
600 140M-I8P-C15 25
480 140M-I8P-C30 42
600 140M-I8P-C30 25
240 140M-I8P-D10 42
480 140M-I8P-C50 42
600 140M-I8P-C50 25
240 140M-I8P-D15 65
480 140M-I8P-D10 65
600 140M-I8P-D10 25
480 140M-I8P-D15 65
600 140M-I8P-D15 25
500-A*/500F-A*/509-A*
500-B*/500F-B*/509-B*
500-C*/500F-C*/509-C*
500-D*/500F-D*/509-D*
500-E*/500F-E*/509-E* 4
0
3
2
1
Specific Notes from SCCR Tables
c)
Number after "H" or "J" can be 2, 3, 6 or 1
General Notes for Short Circuit Current Rating (SCCR) Information
1) The ratings shown are in accordance with UL 508 and CSA 22.2 No. 14
4) The SCCR values listed are kA (1000's amperes) RMS symmetrical
2) The devices and ratings shown are those most commonly needed;
additional ratin
g
s ma
y
be available
3) Additional limitations may apply. Refer to applicable national and local
electrical codes
b)
* Includes all contactor variations following the Size letter, and starter
variations with eutectic or E1 Plus overload relays (except .2 - 1 FLA range)
a)
** Includes suffixes A*, B*, C* & D*. Refer to note b.
d)
For Size 0, combinations with 140U-* circuit breakers include starters with
eutectic overloads (not E1 Plus)
Tightening Torque lb-in (N
s
M)
Catalog
NuMber
For all Catalog NuMbers:
Control Connections Wire Range: AWG 18 -12
Control Connections Tightening Torque: 12 lb-in (1.4 N
s
M)
Power Wires and Tightening Torques
NOTE: Use 60° / 75° C Copper Wire Only.
Contactor
NEMA Size
Wire
Range
(AWG)
Lug to
TerMinal
Wire in
Lug
Overload Relay
to Contactor
500F-
AOD930
14 – 42
500F-
BOD930
500F-
COD930
35 (4.0) 45 (5.1) 35 (4.0)
500F-
DOD930
150 (17.0) 140 (15.8)
500F-
EOD930
14 – 80 - 20 (2.3) 23 (2.3)
1
20 (2.3) 23 (2.3)
14 – 8
-
3 140 (15.8)8 – 1/0
4 200 (22.6) 275 (31.1) 200 (22.6)6 – 4/0