User Manual User guide
Programming Instruction References
A-11
Instruction Description Parameter Valid Addressing
Mode(s)
Valid File Types Immediate
Values
LEQ Less Than or Equal To source A direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
source B direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fmin-fmax
LES Less Than source A direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
source B direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fmin-fmax
LFL
➃
LIFO Load source direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
➄
-32,768-32,767
LIFO array indexed direct
indexed indirect
O, I, S, B, N, A none
LIFO control direct R none
length 1-128
position 0-127
LFU
➃
LIFO Unload LIFO array indexed direct
indexed indirect
O, I, S, B, N, A none
destination direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
➄
none
LIFO control direct R none
length 1-128
position 0-127
LIM
➃
Limit Test (circ) low limit direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fmin-fmax
test direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fmin-fmax
high limit direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fmin-fmax
➃
Supported
only by SLC 5/02, SLC 5/03, and SLC 5/04 processors and MicroLogix 1000 controllers.
➄
Indexed addressing is not allowed when using T