User Manual User guide

Programming Instruction References
A-13
Instruction Description Parameter Valid Addressing
Mode(s)
Valid File Types Immediate
Values
MSG
(5/03 and
Message type 64=peertopeer
(5/03
and
5/04 only)
read/write 0=read, 1=write
target device 2=500CPU,
4=485CIF,
8=PLC5
local/remote 16=local,
32=remote
control block direct N none
control block length 14
channel number 0 or 1
target node 0-31,
0-254 if 485CIF
remote bridge
link ID
0-254,
0 when local
remote bridge
node address
0-254
0 when local
local bridge node
address
0-254, 0xFFFF
when local
local file address direct O, I, S, B, T, C, R,
N, F, A, ST, M
none
target file address direct O, I, S, B, T, C, R,
N, F, A, ST, M
0-255
message length
O, I, S, B, N, A
1-103
F
1-51
T 1-34 or
if PLC5: 1-20
C, R 1-34
ST
2 or
if PLC5: 1
message timeout 0-255
File types F
, A, and ST only apply to SLC 5/03 OS301 or later and SLC 5/04.