The AADvance controller has also been evaluated under certificate IECEx
UL 12.0032X to the standards IEC 60079-0; (5
th
Edition) and IEC 60079-
15 (4
th
Edition).
[ certificate to be supplied]
For a system that is located in a Zone 2 Hazardous environment
where ATEX certification is required, all modules should be installed in an
ATEX or IECEx Certified, tool accessible IP54 enclosure. The enclosure
is to be marked with the following: "Warning - Do not open when
energized". After installation of the modules into the enclosure, access to
termination compartments shall be dimensioned so that conductors can
be readily connected. Modules are for use in an area of not more than
pollution degree 2 in accordance with IEC60664-1