B-12 Enhanced DeviceNet Adapter’s Parameters
13
Fault Cfg A1 In
0 – 65535 0 Yes No
Provides the first word of datalink A data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
14
Fault Cfg A2 In
0 – 65535 0 Yes No
Provides the second word of datalink A data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
15
Fault Cfg B1 In
0 – 65535 0 Yes No
Provides the first word of datalink B data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
16
Fault Cfg B2 In
0 – 65535 0 Yes No
Provides the second word of datalink B data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
17
Fault Cfg C1 In
0 – 65535 0 Yes No
Provides the first word of datalink C data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
18
Fault Cfg C2 In
0 – 65535 0 No No
Provides the second word of datalink C data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
19
Fault Cfg D1 In
0 – 65535 0 Yes No
Provides the first word of datalink D data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
20
Fault Cfg D2 In
0 – 65535 0 Yes No
Provides the second word of datalink D data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
21
Serial Port Rate
9600
19200
9600 Yes Yes
Sets the baud rate for the adapter’s serial/DF1
port.
Important: If you change the baud rate in the
adapter, you must also change it in your
terminal emulation software or terminal.
22
Reset Adapter
Ready
Enable
Set Defaults
Ready Yes No
Ready = No change or reset.
Enable = Resets the module.
Set Defaults = Sets all parameters to their
factory-default values.
# Name
Valid Values/
Settings
Default Writable
Reset or
Power Cycle
Description
Important: For information on accessing and editing parameters, refer to Chapter 3, Configuring the 1203-GU6 Using a Serial
Connection, or Chapter 4, Configuring the 1203-GU6 or 1336-GM6 Adapter Using RSNetWorx for DeviceNet.