Design Installation Guide Owner's manual

Publication DNET-UM072C-EN-P - July 2004
Determine Power Requirements 4-7
Figure 4.4 Two Power Supplies, (One End-Connected, One Middle-Connected);
Two Cable Segments, KwikLink Cable (Flat).
Network
Length
m (ft)
Maximum
Current (A)
220 (722)
8.00*
240 (787)
8.00*
260 (853)
7.91*
280 (919)
7.35*
300 (984)
6.86*
320 (1050)
6.43*
340 (1115)
6.06*
360 (1181)
5.72*
380 (1247)
5.43*
400 (1312)
5.16*
420 (1378)
4.91*
Segment Supply A
Segment A
Segment B
Network
Length
m (ft)
Maximum
Current (A)
0 (0)
8.00*
20 (66)
8.00*
40 (131)
8.00*
60 (197)
7.52*
80 (262)
5.67*
100 (328)
4.55*
120 (394)
3.80
140 (459)
3.26
160 (525)
2.86
180 (591)
2.54
200 (656)
2.29
Network
Length
m (ft)
Maximum
Current (A)
220 (722)
2.08
240 (787)
1.91
260 (853)
1.76
280 (919)
1.64
300 (984)
1.53
320 (1050)
1.43
340 (984)
1.35
360 (1050)
1.28
380 (1247)
1.21
400 (1312)
1.19
420 (1378)
1.09
Segment Supply B
NEC/CE Code Maximum
Current Limit
Exceeds NEC CL2/CECode 4A limit.
Exceeds NEC CL2/CECode 4A limit.
Total Length of trunk line, meters (feet)
Current (amperes)
Network
Length
m (ft)
Maximum
Current (A)
0 (0)
8.00*
20 (66)
8.00*
40 (131)
8.00*
60 (197)
8.00*
80 (262)
8.00*
100 (328)
8.00*
120 (394)
8.00*
140 (459)
8.00*
160 (525)
8.00*
180 (591)
8.00*
200 (656)
8.00*
41934