Design Installation Guide Owner's manual
Publication DNET-UM072C-EN-P - July 2004
Determine Power Requirements 4-13
Section 2 = 140m (2.14A)
Section 1 is overloaded because the total current exceeds the maximum
current (2.85A >
2.14A).
Section 2 is operational since the total current does not exceed the maximum
current (0.75A <
2.14A).
Balance the system by moving the power supply toward the overloaded section
(section 1). Then recalculate each section.
IMPORTANT
Section 1 + Section 2 < 3.6A. This is < 4A for
NEC/CECode compliance.
Results