Configuration Guide Manual
Chapter 4 Configuring FactoryTalk Historian To Historian Interface
20 Rockwell Automation Publication H2H-IN001A-EN-E–July 2012
4. Navigate to C:\Program Files (x86)\Rockwell
Software\FactoryTalk Historian\PIPC\Interfaces\FTPItoPI
and select FTPItoPI.exe.
5. Click Open.
6. Under Host PI Server/Collective, select this computer.
7. Complete the following information:
Under: Type:
Point Source FTSS
Interface ID 1
Service ID 1
8. Click Add.
9. In the PI ICU Register Interface message box, click OK.
10. In the General tab, under General, verify that FTSS is the
Point Source.
11. Under Scan Classes, click
to create one scan class at a 15
second frequency.
12. Under Scan Frequency, type 15.
13. In the PItoPI tab, go to the Required tab, and type the
Source host. It may be either a DNS name or an IP address.